258    CHAPTER 7  Protection and Discrimination























































                         FIGURE 4.7.3
                         Overcurrent protection coordination chart – low voltage system.


                         CT SATURATION

                         It is necessary to check for CT saturation where it is considered to be a likely condi-
                         tion. The saturated CT current may be obtained as follows:
                                           CT rated VA × Accuracy limit factor × CT ratio
                                    I max sat =
                                                 Secondary burden at rated current