Page 375 - Offshore Electrical Engineering Manual
P. 375

362    CHAPTER 4  Protection and Control





                                        A
                                        B
                                        C
                                                                        V 2


                                                                        V 1
                                                                        V
                                   Battery                               1

                                                                        V 2


                                                     –  A  +
                                          Switch
                         FIGURE 7.4.1
                         Circuit diagram for carrying out voltage transformer polarity checks: for the polarity shown,
                         ammeter flicks positive on switch make and negative on switch break.


                         RESTORATION
                           1.   Restore all electrical connections to their correct state after having removed any
                            temporary test wiring.
                           2.   Check all fuses and current limiting resistances, if provided, for continuity, cor-
                            rect rating and good condition. Replace any component which shows signs of
                            thermal or mechanical damage.



                         CURRENT TRANSFORMERS

                         Visual, mechanical, insulation resistance and polarity checking are carried out simi-
                         lar to the methods for the VTs discussed earlier. Fig. 7.4.2 shows the connection
                         arrangements for polarity checking.
                            The following tests should also be undertaken.


                         CURRENT RATIO CHECK
                         There are two methods to perform the check.

                         Method 1
                         This test is performed by secondary injection, as shown in Fig. 7.4.3.
                            Current is passed through two primary windings using a primary injection test
                         set, and the primary and secondary currents are measured. A temporary short-circuit
   370   371   372   373   374   375   376   377   378   379   380