Page 377 - Offshore Electrical Engineering Manual
P. 377

364    CHAPTER 4  Protection and Control




                         of the correct polarity, but will read a value approximating to the CT ratio current if
                         the polarity is incorrect. In some cases, such as in metal-clad switchgear, it may not
                         be possible to access the transformers physically, in which case the protection circuit
                         drawings should confirm that the polarity is correct.

                         Method 2
                         An alternative method is to perform a primary injection test on one CT only, as shown
                         in Fig. 7.4.4. As with method 1, the ratio of primary to secondary test currents should
                         approximate to the transformer ratio marked on the nameplate. For multitapped CTs,
                         the ratio should be checked at each tap.


                         MAGNETISATION CURVE TESTS
                         The CT magnetisation curve should be checked at several points so as to establish the
                         approximate position of the knee point of the transformer.
                            The test circuit for obtaining this point is shown in Fig. 7.4.5. A test volt-
                         age is applied to the CT secondary winding, and the resulting magnetising cur-
                         rent is measured with the primary winding open circuit. The applied voltage is
                         increased gradually until the magnetising current is seen to increase rapidly for
                         small increases in voltage, indicating that the knee point has been reached. The
                         test voltage should then be reduced carefully in stages. The voltage and current
                         should be recorded at several points both above and below the knee point and
                         down to zero test voltage.
                            The knee point is defined as the point on the CT magnetisation curve where a
                         10% increase in applied voltage results in a 50% increase in magnetising current.


                                         A         B         C
                                                                    A 2
                                                                           51
                                                                           51
                                                          P 1  S 1         51

                                A 1                                        64
                                                               S 2
                                                                        Temporary
                                                                        short
                                     Primary injection
                                     test set
                         FIGURE 7.4.4
                         Circuit for current ratio check on current transformer by primary injection (method 2).
   372   373   374   375   376   377   378   379   380   381   382