Page 381 - Offshore Electrical Engineering Manual
P. 381

368    CHAPTER 4  Protection and Control




                                                                      Operating coil B phase
                                             1  2   3  4  5   6  7  8
                             Test block terminals                        9  10
                             (relay)
                                              20 19 18 17   16 15 14  13 12 11
                                 Test plug                  CT shorting links
                                 terminals
                                             1  2   3  4  5   6  7   89     10
                                                                                      A

                             Test block terminals
                             (supply)




                                                     Timer        Relay
                                                     control      current
                                                    Secondary injection unit
                         FIGURE 7.4.7
                         Secondary injection test circuit for triple-pole overcurrent and residually connected earth
                         fault relay.

                           2.   With the TM at 1.0 and 10 times current setting check the operating time against
                            the characteristic once again. In each case, the relay operating time should be
                            within the allowable tolerance band of −7.5% to +7.5%.
                           3.   If the relay is within tolerance the characteristic may be checked over a range
                            of values so that the actual characteristic may be checked against the manufac-
                            turer’s standard.
                           4.   The minimum operating current of the relay should be checked to ensure that it
                            does not exceed the maximum tolerance given by the manufacturer.
                           5.   Check that the maximum current at which the relay will reset immediately
                            following operation (the resetting current) is as stated in the manufacturer’s
                            data.
                           6.   By inspecting the measured characteristic check that the operating time required
                            by the system design, shown in the relay setting schedule, is obtainable.
                           7.   If there are any attracted armature and/or electronic instantaneous elements
                            in the relay, these should be tested for pickup (i.e., operation at the minimum
                            specified voltage or current). Attracted armature relays used for this purpose
                            are designed so as not to chatter, and if chatter occurs, it is likely that the relay
                            contacts need to be cleaned.
                           8.   Auxiliary relays for operation of flag indicators, remote indication circuits, etc.
                            may require a separate supply in order to be tested.
   376   377   378   379   380   381   382   383   384   385   386