Closing and Tripping  373




                  CLOSING AND TRIPPING

                  The protection relays are fault sensing devices and cannot interrupt fault currents
                  themselves. Therefore it is vital that the operation of the devices which perform
                  this duty, i.e., the circuit breakers and their tripping and closing control circuits,
                  are checked with their associated protection relay schemes. For the circuit breakers
                  to be operated, it is necessary to commission the tripping and closing batteries and
                  chargers before the primary injection test. An auxiliary DC supply is often required
                  by the protection relays, in any case, for the operation of indication devices and as
                  power supplies for electronic relays.
                    All auxiliary relays associated with each circuit breaker control system, including
                  lockout relays and intertripping and interlocking schemes, should be functionally
                  tested before the circuit breaker is put into service.