Page 388 - Offshore Electrical Engineering Manual
P. 388

CHAPTER
                                                                             5
                  Large Motors









                  PRECOMMISSIONING
                  Before commissioning, it is essential that the installation work has been properly
                  checked before any equipment or cables are energised, or anything is allowed to
                  rotate. Cable connections are ‘rang through’ and cable insulation is checked. All such
                  work is termed precommissioning.



                  MOTOR COMMISSIONING TESTS
                  Three types of testing are recommended for the offshore commissioning of
                  motors.


                  MEGOHMMETER (MEGGER) TEST
                  This involves the direct current (DC) measurement of the stator winding resis-
                  tance to earth and between phases at the appropriate test voltage as shown in
                  Table 7.5.1.
                     This test is carried out on all motor windings and is of 1 min duration.
                     The procedure is as follows:

                    1.   Disconnect the neutral point and adequately insulate each phase lead from earth.
                     On small machines, it will not be possible to disconnect the neutral point.
                    2.   Disconnect and earth all resistance temperature devices (RTDs).
                    3.   Ensure that the motor frame is connected to a known earthing point. Phases not
                     under test must be earthed.
                    4.   Measure the ambient air temperature in degree Celsius local to the motor before
                     starting the test. If the temperature of the motor is thought to be significantly
                     higher than the motor air temperature, then the winding temperature should be
                     measured, if possible, by using any RTDs fitted to the motor before they are
                     disconnected for the test.
                    5.   If the temperature of the insulation is cold to the extent that it is below the dew
                     point, a moisture film will form on its surface and may lower the insulation
                     resistance, especially if the winding has developed a coating of dirt and/or salt.
                     Therefore, if this is likely to occur, the motor anticondensation heaters should
                     be left on for some time before the motor is tested.


                  Offshore Electrical Engineering Manual. https://doi.org/10.1016/B978-0-12-385499-5.00044-3  375
                  Copyright © 2018 Elsevier Inc. All rights reserved.
   383   384   385   386   387   388   389   390   391   392   393