Page 390 - Offshore Electrical Engineering Manual
P. 390

Motor Commissioning Tests  377




                   Table 7.5.2  Winding Temperature Coefficients for Insulation Resistance
                   Measurements at Various Temperatures

                   Winding Temperature (°C)         Multiplier Coefficient k t
                   0                                 0.06
                   10                                0.12
                   20                                0.25
                   30                                0.5
                   40                                1.0
                   50                                2.0
                   60                                4.0
                   70                                8.0
                   80                               16.0
                   90                               32.0
                   100                              64.0


                     The PI can be calculated as follows:
                                               10 ‐ min reading
                                           PI =
                                               1 ‐ min reading

                     In the case of low-voltage machines, i.e., machines whose rated voltage is 600 V
                  or less, the PI is calculated using the 30-s and 1-min readings and the application
                  time is limited to 1 min.

                  OVERPOTENTIAL TESTS
                  Overpotential tests should not be carried out on motors unless the insulation resis-
                  tance is greater than 100 MΩ and the PI values are greater than 2.0 for class B and
                  class F insulation, or 1.5 for class A insulation.
                     High DC voltages are both lethal and, if the motor under test is in an area where
                  flammable gases may be present, an ignition hazard. Carefully follow all operational
                  procedures and safety precautions.
                     High-voltage DC tests should be applied as specified in Table 7.5.3, and the
                  test should be made between the windings under test and the frame of the machine
                  (which must be adequately earthed).
                     The test procedure is as follows. To start with, a test voltage of preferably about
                  one-third but not more than one-half of the full test voltage quoted in Table 7.5.3 should
                  be applied. This should be increased to the full test voltage as rapidly as the indicat-
                  ing instrument will allow without overshooting beyond the quoted value. The full test
                  voltage must be maintained for 1 min, and the leakage current recorded. At the end of
                  1 min, the test voltage must be reduced rapidly to not more than one-third of its full
                  value before switching off. This method of test voltage application is important to avoid
                  overstressing the insulation with high transient voltages produced by switching, etc.
   385   386   387   388   389   390   391   392   393   394   395