Page 391 - Offshore Electrical Engineering Manual
P. 391

378    CHAPTER 5  Large Motors




                          Table 7.5.3  High-Voltage DC Tests
                                                             Maximum Recommended DC High-
                          Machine Rating                     Voltage Tests (V)

                          Less than 1 kVA (or kW) with rated voltage   500 + (2 × rated voltage)
                          below 100 V
                          Less than 1 kVA (or kW) with rated voltage   1000 + (2 × rated voltage)
                          100 V and above
                          1 kVA (or kW) and above, but less than   1000 + (2 × rated voltage)
                          10 MVA (or MW)
                          10 MVA (or MW) and above, at rated voltages
                          Up to 2 kV                         1000 + (2 × rated voltage)
                          Above 2 kV and up to 6 kV          2.5 × rated voltage
                          Above 6 kV and up to 17 kV         3000 + (2 × rated voltage)
                          Above 17 kV                        Subject to special agreement


                            Earths should be applied to each test winding for at least 10 min after completion
                         of the test and the complete windings for 1 h after final completion of all tests.
                            BS EN 60034:18-31:2012 permits DC onsite high-voltage tests to be carried out
                         by agreement between the manufacturer and the purchaser. The test voltages must
                         not be greater than 1.6 × 0.8 (i.e., 1.28) times the root mean square (RMS) value of
                         the alternating current voltage specified in BS EN 60034. The values recommended
                         in Table 7.5.3 are the RMS values quoted and are therefore 80% of the maxima
                         allowed. These values must still be agreed with the machine manufacturer, however,
                         before testing is undertaken.


                         EVALUATION OF MOTOR TEST RESULTS
                         When the tests described earlier have been carried out, the results must be interpreted
                         to make a decision on whether or not to accept the machine for operation. An esti-
                         mation of the machine’s acceptability may be based on a comparison of present and
                         previous values of insulation resistance and PI, corrected to 40°C in each case.
                            When the insulation history is not available, recommended minimum values of
                         PI or of the 1-min insulation resistance value may be used. These values are given
                         in Table 7.5.4.
                            The insulation resistance value of one phase of a three-phase winding, with the other
                         two phases earthed, is approximately twice of that of the entire winding. Therefore, when
                         the three phases are tested separately, the observed resistance of each phase should be
                         halved to obtain a value for comparison with the appropriate value in Table 7.5.4(a).
                            The acceptance criteria in Table 7.5.4 must be modified, however, owing to the
                         following  limitations.  First, insulation  resistance  is not  directly  related  to  dielec-
                         tric strength, and it is therefore impossible to specify the value at which a winding
                         will fail electrically. Second, the windings of large or slow-speed machines have
                         extremely large surface areas, with healthy values of insulation resistance less than
                         the recommended minimum.
   386   387   388   389   390   391   392   393   394   395   396