Page 389 - Offshore Electrical Engineering Manual
P. 389

376    CHAPTER 5  Large Motors




                          Table 7.5.1  DC Megohmmeter and Polarisation Index Tests for AC Motors
                          Motor Rated AC Voltage DC Test   Motor Rated AC Voltage DC Test
                          Voltage (V)                      Voltage (V)

                          Below 100                        500
                          Above 100 and up to 600          1000
                          Above 600 and up to 5000         2500
                          Above 5000                       5000

                                                     IEEE 43-2000
                                                           Insulation Resistance Test Direct
                          Winding Rated Voltage (V)        Voltage (V)
                          <1000                            500
                          1000–2500                        500–1000
                          2501–5000                        1000–2500
                          5001–12,000                      2500–5000
                          >12,000                          5000–10,000
                          AC, alternating current; DC, direct current; IEEE, Institute of Electrical and Electronics
                          Engineers.


                           6.   With a Megger or similar instrument perform the following test using the volt-
                            ages given in Table 7.5.1. With the neutral point disconnected test the phase-to-
                            phase insulation by applying the test voltage to each phase in turn with all other
                            phases earthed. This test measures the combined insulation resistance of the
                            tested phase, both to earth and to the other (earthed) phases.
                           7.   Again using Table 7.5.1, with the neutral point connected, test the winding insu-
                            lation to earth by applying the test voltage to each phase winding connection in
                            turn, with all other phase connections insulated from earth. The winding insula-
                            tion resistance should be corrected to 40°C by using the equation R  = K R ,
                                                                                  c
                                                                                     t t
                            where R  is the insulation resistance corrected to 40°C, R  is the insulation
                                   c
                                                                          t
                            resistance at temperature t in °C and K  is the insulation resistance temperature
                                                           t
                            coefficient at temperature t obtained from Table 7.5.2.
                         POLARISATION INDEX
                         This test is a continuation of the above-mentioned Megger test and requires the appli-
                         cation of the appropriate test voltage for 10 min. The ratio of the 10-min to the 1-min
                         reading is termed the polarisation index (PI) and gives some indication of the dryness
                         of the windings and their ability to withstand overvoltage tests.
                            The procedure is as follows. Using a motor-driven Megger or similar instrument
                         measure the resistance to earth and between the phases of the motor windings. The
                         test voltage (obtained from Table 7.5.1) should be applied for 10-min readings and
                         those noted after 1 and 10 min.
   384   385   386   387   388   389   390   391   392   393   394