Page 90 - Offshore Electrical Engineering Manual
P. 90

Switchboard Construction   77




                  of this between fault inception and contact opening. Generator ac decrement must
                  also be taken into account. Providing the switchgear fault make rating is adequate;
                  problems with fault break ratings may be overcome by delaying the circuit breaker
                  opening until the fault current has decayed to a value within the rating. The use of
                  bus bar reactors is not recommended due to offshore weight and space limitations.
                  Because of the high prospective fault currents, it is likely that any large motors sup-
                  plied directly from this switchboard will require circuit breaker rather than fused
                  contactor switching. To avoid shutting down generators or other vital equipment to
                  carry out maintenance on the switchboard, a duplicate busbar switchboard may be
                  considered. This is not often specified, however, because of the extra complexity,
                  cost, weight and space involved. If it is likely that further generators will be required
                  to be installed, due to a later operational phase such as artificial lift, then the switch-
                  board will require to be rated for this future load and fault rated for the future pro-
                  spective fault current capacity of the expanded system. Sufficient spare equipped
                  circuit breakers should be provided for the expansion.


                  LARGE DRIVE SWITCHBOARDS 3.3–6.6 KV
                  Development of motor controlgear at up to 6.6 kV has resulted in very compact units
                  where relatively low load currents are switched by vacuum contactors protected from
                  short circuit faults by suitable HRC fuses. For incoming and outgoing distribution,
                  circuit breaker cubicles are provided, the whole forming a composite switchboard of
                  low weight and compact dimensions. The prospective fault level on this switchboard
                  can be regulated to some extent by adjusting the reactance of the supply transformer
                  windings. Therefore, motor control is usually by fused contactor rather than circuit
                  breaker.


                  UTILITY SERVICES AND PRODUCTION SWITCHBOARDS
                  Because of the interdependence of various systems on an offshore installation, as can
                  be seen by the examples in PART 1 Chapter 2, the low voltage switchboards must be
                  considered as just as vital as their medium voltage neighbours. Maintenance of cir-
                  cuits for such supplies as machinery auxiliaries and hazardous area ventilation must
                  be given high priority. An example of a generator lube oil auxiliary system is given
                  in PART 2 Chapter 4.


                  EMERGENCY SWITCHBOARDS
                  The function of the emergency switchboard is described in PART 1 Chapter 1.
                     It is beneficial to provide synchronising facilities for the switchboard’s associ-
                  ated emergency generator. The generator has automatic start facilities which will
                  initiate a start following a main generation failure, provided the start signal is not
                  inhibited by one of the safety systems. The synchronising facility gives a conve-
                  nient means of routine load testing for the generator, and allows for changing over
   85   86   87   88   89   90   91   92   93   94   95