Page 89 - Offshore Electrical Engineering Manual
P. 89

76     CHAPTER 5  Generation and Distribution Switchgear and Transformers




                            It is also important that facilities for cabling are as flexible as possible, and that
                         sufficient space is available for installation of the largest cables without exceeding
                         bending radii limits. Neutral connection arrangements for outgoing supplies with
                         neutrals must be provided. Facilities need to be provided for the earthing of cable
                         armour. If cable entry is at the top, there should be no risk of moisture entering via
                         the cable entry even if the cables do not have drip loops.
                            The space requirements for circuit breaker handling trucks must not be forgot-
                         ten. Functional test facilities should be built in to the switchboard using a test panel
                         cubicle with bus wiring to each unit to avoid dangerous trailing leads. The test facil-
                         ity must be interlocked to ensure that live operation of field equipment is impossible
                         using the test panel. Every unit on the switchboard will require suitable permanent
                         labeling and interlocking, shuttering and maintenance padlocking facilities. In fact,
                         all the usual requirements for onshore substations such as safety rubber matting,
                         earthing facilities and safety testing equipment will be required.
                            Fault calculations are covered in PART 4 Chapter 6.
                            Protection relay schemes are covered in PART 4 Chapter 7.


                         MAIN SWITCHBOARDS 6.6–13.8 KV

                         The overriding consideration for any main switchboard must be the short circuit
                         capability of the circuit breakers, because of the fault current capability and proxim-
                         ity of the installed generation. Generator operational configurations which produce
                         prospective fault MVAs of more than 1000 should be avoided as downstream equip-
                         ment and cables would require to be of special nonstandard manufacture with all the
                         expensive development and testing this would entail, in order to obtain sufficient
                         rating.
                            The following are typical examples of switchgear presently available:

                                                           Maximum Fault    Max. Operating
                          Manufacturer     Type            Capacity (kA)    Voltage (kV)

                          ABB              Unigear (air    31.5             46
                                           insulated)
                          ABB              ZX (gas insulated)  40           40
                          ABB              Is Limiter a    210              40.5
                          GE (USA)         SecoGear (vacuum)  40            17.5
                          Powell           PowlVac (vacuum)  63             15
                          Mitsubishi Electric  MS-E        40               15
                          Schneider Electric  F400 (vacuum/SF6)  40         40.5
                          Siemens          8DA10/8DB10     40               42
                                           (vacuum/SF6)

                          a Recommended for upgrade projects only, where original fault ratings are exceeded.
                            As discussed earlier in the chapter, a check will have to be made to ensure that the
                         asymmetrical breaking capacity is adequate, allowing for the decrement in the value
   84   85   86   87   88   89   90   91   92   93   94