Page 84 - Offshore Electrical Engineering Manual
P. 84

Types of Interrupter  71




                  MAKING CURRENT
                  The most onerous fault for a circuit breaker to handle is where a short circuit
                  fault exists on a part of the system which is isolated from the generator(s), and
                  the intervening circuit breaker is closed. This would mean that the full system
                  voltage is applied with no decrement. If the fault is close to the circuit breaker,
                  then the intervening impedance is small, giving the highest instantaneous current
                  flow.




                  TYPES OF INTERRUPTER
                  HRC CARTRIDGE FUSES
                    1.   A fuse is basically a device with a central conductor that is designed to melt
                     under fault conditions. Interruption is achieved by spacing the two ends suf-
                     ficiently far apart for the arc to be naturally extinguished. However, to obtain
                     a consistent performance characteristic, fuse elements are carefully designed
                     for particular voltage and current ratings. The ceramic cartridge tube is filled
                     with powdered quartz and sealed. The silver element is not a continuous strip of
                     silver, but is necked in short sections to reduce pre-arcing time. It may also have
                     sections of low melting point, ‘M’-effect material, to improve performance at
                     low fault levels (see Fig. 2.5.4).
                    2.   The physical design of the element such as the length and shape of the necks
                     will depend on the application of the fuse and its operating voltage. If the
                     maximum arc voltage is exceeded, the pre-arcing time will be reduced and
                     the fuse will not operate according to its standard characteristic. Since a fuse
                     is purely a means of protection against overload and fault currents, isolators
                     or contactors are installed in series to carry out normal switching
                     operations.
                    3.   The advantage in using fuses is that the resulting switch-fuse device is often
                     less expensive, smaller and lighter than the equivalent circuit breaker, particu-
                     larly in the higher power ranges. Exceptions to this for low voltage distribution
                     equipment are some of the higher performance current limiting miniature circuit
                     breakers. These will be discussed later in the chapter.
                    4.   The disadvantages with fusegear are:-

                     a. HRC fuses must be replaced, once operated and no matter how reliable the
                       circuit is, some holding of spare fuses will be necessary and replacement
                       of the larger bolted fuses is time-consuming. Permanent power fuses are
                       available, which use the thermodynamic characteristics of liquid sodium to
                       interrupt fault currents for a few milliseconds during which time a suitable
                       switching device is operated to isolate the faulty circuit. This type of fuse is
                       not (to the author’s knowledge) used offshore.
                     b. The standard ranges of fuses available are limited in current and fault capac-

                       ity below the maximum ratings available in switchgear ranges.
   79   80   81   82   83   84   85   86   87   88   89