Page 237 - Pipeline Rules of Thumb Handbook
P. 237

224     Pipeline Rules of Thumb Handbook

                  Signal attenuation coating survey            number of categories relating to “point” anomalies or “general
                                                               area” anomalies. For example, the following categories may
           Results are presented in graphical form although quick  be used.
         analysis may be performed in the field from raw data. Areas
         of poor coating quality may be readily identified from final  Classification         Definition
         graphs.                                               Type I        Both the “ON” and “OFF” potentials are
           Following the production of graphs and histograms an              more positive than preset criteria. There is
         evaluation system employed in pipeline coating quality              little or no “IR” voltage. The potentials are
         assessment may assign values to the level of signal loss and        unsatisfactory and the locations are not
         the measurement distance interval. The sum of the two val-          cathodically protected.
         ues referred to as the “dB factor” and the “km factor” may be  Type II  The “OFF” potential is more positive than a
         used to indicate the future action required and the level of        preset limit, the “ON” potential more nega-
         priority for each section surveyed.                                 tive. There is a reduced level of protection
           The evaluation of the coating quality is illustrated in Figure    indicated at “point” locations which may be
         1. It should be noted, however, that gradings assigned to one       improved by increased output from the
         particular pipeline cannot be compared to those assigned to         nearest cathodic protection station, although
         another.                                                            where this occurs over long pipeline lengths,
                                                                             it indicates high resistance coating or soils.
                                                               Type III       Positive change in the “ON” and “OFF”
                                                                             potential plot where both remain more
                    Close interval potential survey
                                                                             negative than the selected criteria. This
                                                                             indicates increased current demand at these
           Results are shown in graphical form. Defect location is
         undertaken after the survey and requires experienced per-           locations but that protection is maintained at
                                                                             a satisfactory level.
         sonnel to interpret the results.                      Type IV        Unusual potential variations due to outside
           The achievement of cathodic protection on the pipeline is
         indicated by the “ON” and “OFF” potential both being more           influences, e.g., stray currents, station earth-
                                                                             ing, AC induced voltages.
         negative than the accepted criteria.                  Type V        A change in level of the “ON” potential at a
           Pipeline locations with inadequate cathodic protection will
         be indicated by the graph “ON” and “OFF” potentials shift-          test post due to the change in the length of
                                                                             that part of the measuring circuit passing
         ing to a less negative level and become cause for concern if        current, i.e., increasing “IR” volt drop due
         the “OFF” potentials are more positive than say -0.85V.             to increasing pipe length in circuit.
           It is considered that a localized coating defect would nor-
         mally be indicated by a sharp positive shift of the “ON” poten-  Of the five categories listed above the first three are
         tial plot coupled with a plot shift of smaller amplitude of the  indicative of coating defects. Types IV and V are commonly
         “OFF” potential, i.e., that the potential difference (IR drop)  observed on close interval potential survey results and require
         between the “ON” and “OFF” reading decreases, indicating  careful interpretation.
         a reduced coating resistance at that point.             It is important that these considerations are borne in mind
           The “OFF” potential plot change would not be as large as  when selecting the survey or combination of surveys to be
         that of the “ON” potential, as the “OFF” potential would be  employed and in addition the choice of which survey to
         the polarized (or partially polarized) potential of the bare  employ and when to employ it is dependent on a number of
         steel. This differs from the case where insufficient current for  factors, namely,
         the achievement of polarization is available.
           In all these cases, the IR drop measured between the “ON”  • the purpose of the survey,
         potentials and the “OFF” potentials includes, along with the  • the condition of the pipeline,
         resistance of the coating, the resistance of the soil. The resis-  • the access over the pipeline,
         tance of the coating is assumed to be the largest component  • the time allowed.
         of this resistance value.
           Current is also a factor of the IR value. The current den-  As the protection system relies on both the external coating
         sity impressed on the pipeline will increase as the cathodic  and a cathodic protection system, these may be considered as
         protection stations are approached, giving the largest “I”   first and second lines of defense against corrosion. It is pos-
         value of the IR drop near the location of the negative   sible to take the position that concern over damaged coating
         connection.                                           is not warranted as back up from the cathodic protection
           In order to interpret the data obtained fully, the anomalies  system is available and therefore the integrity of the pipeline
         observed in the plotted results may be classified into a  is not at risk. If this attitude is taken, then obviously close
   232   233   234   235   236   237   238   239   240   241   242