Page 354 - Power Electronic Control in Electrical Systems
P. 354

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH008.3D ± 338 ± [290±372/83] 17.11.2001 10:29AM







               338 Transient studies of FACTS and Custom Power equipment






















                      Fig. 8.56 Test system used to carry out the DVR transient analysis.




                        The simulation scenarios are as follows:
                        (i) In the first simulation the DVR is disconnected and a three-phase short-circuit
                           fault is applied at point A, via a fault resistance of 0:66 
, during the interval
                           0.8±1.0 s. The voltage sag at the load point is 25% with respect to the reference
                           value.
                        (ii) The second simulation is carried out using the same scenario as above but now
                           with the DVR in operation.

                      Figures 8.57 and 8.58 show the digital implementation in PSCAD/EMTDC of the
                      power system and the DVR controller. Using the facilities available in the simulator,
                      the DVR is simulated to be in operation only for the duration of the fault, as it is
                      expected in a practical situation. The results for both simulations are shown in Figure
                      8.59. When the DVR is in operation, the voltage sag is mitigated almost completely,
                      and the voltage V rms at the load point is driven back to the reference as shown in
                      Figure 8.59(b). The PWM control scheme controls the magnitude and the phase of
                      the injected voltages, restoring V rms . The sag mitigation is performed with a smooth,
                      stable and rapid DVR response; acceptable overshoots are observed when the DVR
                      comes in and out of operation. Figure 8.60 shows the V a voltage at the sensitive
                      load point. Figure 8.60(a) shows the voltage V a when the DVR is not in operation
                      (Brk1 open). When Brk1 is closed and the DVR is connected in series with Load 1 the
                      voltage sag is mitigated as shown in Figure 8.60(c). A slight increase in the peak
                      value of the waveform is observed compared to the case when the DVR is not in
                      operation.
                        This effect is purely due to the harmonic distortion generated by the DVR.
                      However, the rms voltage is kept very close to the reference value as shown in Figure
                      8.59(b). The voltage injected by the DVR in phase a is shown in Figure 8.60(b). It
                      should be noted that no filters are used in the simulations with a switching frequency
                      of f sw ˆ 450 Hz.
   349   350   351   352   353   354   355   356   357   358   359