Page 167 - Power Electronics Handbook
P. 167

Phase control   159
                     To derive the rating of the devices let Vbe the r.m.s. input voltage to the
                   a.c.  lines, R  the load resistance, and a the firing angle delay. Then the
                   r.m.s.  current  rating of  each thyristor and  diode  in  Figures 8.l(a)  and
                    8.l(b)  is given by equation (8.1).







                            = - [1--+-  sin 2a       I”
                                           a
                                 V
                               JWR         n2Jt
                     For Figure 8.l(c) the diodes conduct only in each half cycle, so that their
                   rating is given by equation (8.1), but the thyristor conducts during both
                   half cycles so equation (8.1) must be multiplied by a factor V2. If a triac is
                   used  in  Figure 8.l(a) in  place of  the  two  thyristors then  it  also carries
                   current in both half cycles, and the same multiplying factor must be used
                   when obtaining its rating.
                     It was mentioned in Chapter 1 that thyristor ratings can conveniently be
                   obtained on an r.m.s.  basis, except at very low conduction angles. At these
                   control settings the ratio of peak to r.m.s. current is large and care must be
                   taken not to exceed the repetitive peak current. All devices must be rated
                   to withstand a peak repetitive voltage of  Vq2.
                     The r.m.s. load voltage and currents are similarly given by equation (8.2)
                   and it is seen from these equations that for a = 0 the values of current and
                   voltage are those of the sine wave input.
                                                 ”

                     V,  = [ 1 [ V42) sin’  0 de]
                             Jr
                                 a
                                              1”






                              L               J
                     The load voltage and current waveforms shown in Figure 8.l(d) are rich
                   in harmonics, and Figure 8.2 gives the Fourier analysis of  the spectrum up
                   to the seventh.  Where  load harmonics must be minimised a.c.  chopper
                   regulators are preferred, as described in Section 8.3.
                     It  was  mentioned  in  Chapter  6 that  for  inductive loads  the  control
                   thyristors do not cease conduction when the input voltage reverses, but are
                   kept  on by  energy stored in  the  load, which is fed back  to the supply.
                   Figure 8.3 shows the modified waveforms for a series resistance-induct-
                   ance load of power factor angle +. Thyristor TH1 in Figure 8.l(a) is fired at
                   time tl, which causes the load current to flow, the rising edge of the current
                   being  slower  than  for  a  purely  resistive  load.  Thyristor  THI  is  kept
                   conducting until time tZl, energy flowing from the load to the supply from
   162   163   164   165   166   167   168   169   170   171   172