               The trickle charge and quick charge voltage per cell of the above batter-
            ies shall be 2.15 2.25 6 0.02 V and 1.85 2.75 V respectively. The range of
            charging current of the batteries shall be as follows:
              For 300 Ah battery: Boost charge 42 21 A and float charge 720 240 mA
              For 400 Ah battery: Boost charge 56 28 A and float charge 960 320 mA
              For 200 Ah battery: Boost charge 28 14 A and float charge 480 160 mA
               The minimum demand load on the chargers are:

              Charger for 300 Ah battery: 24 A
              Charger for 400 Ah battery: 40 A
              Charger for 200 Ah battery: 16 A