172  Practical Power System and Protective Relays Commissioning
















            FIGURE 16.14 Phase to phase to earth fault.



















            FIGURE 16.15 Single-phase open-circuit fault.

            16.4.4 Unsymmetrical Single-Phase Open-Circuit Fault
            Analyses
            This fault is unsymmetrical as it is on one phase only and can be analyzed as
            follows (Fig. 16.15):

                                      I 2 1 I 0 52 I 1



            16.4.5 Three-Phase Equivalent Fault Level and Fault Current
            To make the calculation simple, a single-phase fault can be represented
            approximately as three-phase faults, for example:
                                            h        i
               MVA 3Φ equivalent to 1Φ fault 5 3  MVA b 3 100
                                               2Z 1 1 Z 0
                                      MVA3Φequivalent
                                  I F 5     p ffiffiffi
                                             3V L
               Sequence voltages for different fault types.