170  Practical Power System and Protective Relays Commissioning


               Negative-sequence impedance:

                                         Z 2 5 Z 1
               Zero-sequence impedance:
               Z 0 can be calculated or determined by testing.
               Synchronous generator sequence impedances are now described.
               The positive-sequence impedance of a generator is approximately equal
            to: Xs (steady state reactance).
               The negative-sequence impedance of a generator is approximately equal
            to: Xsv (sub transient reactance).
               The zero-sequence impedance of a generator is approximately equal to:
            XL (leakage reactance).



            16.4 SYMMETRICAL THREE-PHASE FAULT ANALYSES
            This type of fault is a symmetrical fault as it is on the three phases at the
            same time as shown below (Fig. 16.11):
                              V R 5 V Y 5 V B ;  I R 1 I Y 1 I B 5 0
                                             E
                                       I 1 5
                                           Z s 1 Z 1



            16.4.1 Unsymmetrical Single-Phase Fault Analyses

            This fault is unsymmetrical as it is on one phase and earth, and can be ana-
            lyzed as follows (Fig. 16.12):
                        V R 5 0;  I Y 1 I B 5 0;  I 1 5 I 2 5 I 0 ;  I R 5 3I 1

                                             E
                                    I 1 5
                                        3Z s 1 2Z 1 1 Z 0
                                        I F 5 3 I 0













            FIGURE 16.11 Three-phase fault.