Page 174 - Practical Power System and Protective Relays Commissioning
P. 174

174  Practical Power System and Protective Relays Commissioning


                  For example, a 240 MVA SGT has a name plate rating of 20%;
                                                    20 3 100
                               Rating on 100 MVA  5
                                                      240
                                                  5 8:33%
            2. MVA
                  Fault rating and fault in-feed are expressed in MVA. This is related to
               percent impedance by the following:
                     Percent impedance 5 10; 000=MVA if the base is 100 MVA
                  For example, if the fault infeed at a particular substation is 35,000
               MVA, then the source impedance, expressed as a percentage on 100
               MVA base, will be 0.286.
                  Similarly, if it is calculated that the impedance to a particular fault is
               2% (on 100 MVA), then the fault infeed will be 5000 MVA.
                  To derive the fault current (I f ), either:
               a. Use I f 5 fault infeed (MVA)/(kV 3 1.732) kA
               b. Or I f 5 10,000/(kV 3 1.732 3 Z%) kA
            3. Ohmic impedance
               To convert percent impedance to primary ohmic impedance:

                        Taking Z%  5 percent impedance on 100 MVA
                                       10 4
                        Z%         5
                                      MVA
                                      V2
                        MVA        5
                                      Z
                                        4
                                      10 3 Z
                        Z%         5
                                        V 2
                                                 2
               Then, primary impedance (Ω) 5 Z% 3 (kV /10,000)
               For example: if Z% 5 2, and kV 5 400, then Z prim 5 32 Ω.
                                            2
               Conversely, Z% 5 Z prim (10,000/kV ).
               To convert primary ohmic impedance to secondary ohmic impedance,
            this can be done by using the following impedance conversion factor
               This depends upon the VT and CT ratios, as follows:
                              Z sec 5 Z prim 3 ðCT ratio=VT ratioÞ
               For example, for 400 kV, with 2000/1 CTs:

                             Z sec 5 Z prim 3 ð2000 3 110=396; 000Þ
               General notes for calculating the impedance to fault and fault current
            are described here. To calculate the fault current, it is first necessary to
            draw out the network involved. From this the impedance network is
   169   170   171   172   173   174   175   176   177   178   179