Protection Relays Chapter | 18  207









































             FIGURE 18.5.8 30 degrees connection maximum torque angle at zero degree.

               TABLE 18.5.3 30 Degrees Connection Zero Degrees Maximum Torque
               Angle Connections
               Relay               Current               Voltage
               R                   I R                   V RB
               Y                   I Y                   V YR
               B                   I B                   V BY


                Refer to Fig. 18.5.9 for directional relay connections and to Fig. 18.5.10
             for a residual voltage connection.
                The recommended MTA for directional relays is as follows:
                Zero degree for resistance-earthed systems;
                Forty five degrees for lag power factor distribution system solidly earthed;
                Sixty degrees for lag power factor transmission systems solidly earthed.