216  Practical Power System and Protective Relays Commissioning















































            FIGURE 18.6.9 Special distance relay characteristic used as a remedial for load encroach-
            ments and arc fault resistance effect.
               transmission line and will not trip for a fault which it is required to trip
               on (refer to Fig. 18.6.10).
               As a fault on the transmission line with fault impedance Z with the effect
            of fault resistance, R f will be seen by the relay as Z x and cause the relay not
            to trip on this fault.
               To avoid this problem of arc fault resistance we use the quadrilateral
            characteristic as shown in Fig. 18.6.9.
               In general, distance relay has different characteristics depending on the
            application as shown in Fig. 18.6.11.