Page 255 - Practical Power System and Protective Relays Commissioning
P. 255

252  Practical Power System and Protective Relays Commissioning

























            FIGURE 18.9.1 Schematic illustrating area of a busbar zone.


               Good busbar protection will have the following features:
               Main and check zones;
               Block in case of CT open circuited;
               Very fast;
               Very good stability;
               Selective tripping for the faulted section only;
               Good isolation facilities and short circuit facilities for CTs during testing.

            18.9.3 BUSBAR PROTECTION TYPES

            1. Frame leakage;
            2. Busbar blocking;
            3. Busbar differential protections
               A. Low-impedance biased differential
               B. High-impedance differential;

            18.9.3.1 Frame Leakage Busbar Protection

            This involves measurement of the fault current from the switchgear frame to
            the earth. It consists of a CT connected between frames to earth points and
            energizes an instantaneous earth fault relay to trip the switchgear. It
            generally trips all the breakers connected to the busbars.
               Care must be taken to insulate all the metal parts of the switchgear from
            the earth to avoid spurious currents being circulated. A nominal insulation of
            10 MΩ to earth is sufficient. The recommended minimum setting for this
            protection is about 30% of the minimum earth fault current of the system
            (see Fig. 18.9.2).
   250   251   252   253   254   255   256   257   258   259   260