Page 258 - Practical Power System and Protective Relays Commissioning
P. 258

Protection Relays Chapter | 18  255


             18.9.3.3.1 Low-Impedance Busbar Prottection
             Low-impedance busbar protection uses the Merz-price circulating current
             principle for biased differential protection to detect a fault in the busbar
             zone, as shown in Fig. 18.9.5.
























             FIGURE 18.9.5 Low-impedance biased differential protection for busbars.
                As shown in Fig. 18.9.5, for a fault F 1 the relay will trip, but for F 2 the
             relay will be stable due to the effect of the relay restraining coil. The operat-
             ing time of this relay is in the range of 20 ms.

             18.9.3.3.2 High-Impedance Circulating Current Protection
             Refer to Figs. 18.9.6 and 18.9.7 for a high-impedance differential protection
             scheme.
                V relay 5 I 1 3 (R CT1 1 R L1 ), V relay 5 I R 3 R
                R 5 V relay/I R then R 5 (I 1 3 (R CT1 1 R L1 ))/I R
                                I 1 3 ðR CT1 1 R L1 Þ
                            R 5               ; R st 5 R 2 R relay
                                      I R
             where V relay 5 voltage across the relay during the external fault F;
             R st 5 stabilizing resistor; R CT 5 CT winding resistance; R L 5 lead resistance.
                For maximum external fault F, the current in relay R is theoretically zero,
             where R L1 , R L2 are lead resistances, R CT is the CT resistance, if one CT becomes
             fully saturated in one side its secondary EMF will become zero and this can be
             represented as short circuited across its magnetizing impedance. This is the worst
             case for stability of high-impedance relay and the relay must be stable under this
             condition for the maximum external fault. Under this condition the current I 1
             will pass through the relay circuit and the saturated CT SC branch.
                Where  I R 5 relay  current  setting,  R 5 relay  circuit  impedance,
             V s 5 setting voltage, V R 5 relay voltage,
                Then V R 5 I 1 (R CT 1 R L1 )
   253   254   255   256   257   258   259   260   261   262   263