Protection Relays Chapter | 18  269
































             FIGURE 18.11.3 Breaker failure scheme.
             current detector contact (OC) closes if the current is still passing, which
             means that when breaker 1 fails to trip after time T expires, the BF relay
             also sends a retrip to breaker 1 and a trip signal to trip breaker 2 and breaker
             3 to stop the fault current flow and send a trip signal to the remote end of
             the line if this end feeds the fault.
                BF relay time setting is set in the range of 110 180 ms, some utilities
             are at set 125 ms and others at 140 ms. This will be explained in the BF set-
             ting chapter of this book (Sub-chapter 19.7.3).
                The total fault clearing time of BF relay is about 260 300 ms, as
             explained in the BF setting chapter of this book (Sub-chapter 19.7.3).


             Subchapter 18.12


             Transformer Protection


             18.12.1 INTRODUCTION
             Transformer faults can be classified as follows:
                Winding and terminal faults;
                Core faults;