Page 280 - Practical Power System and Protective Relays Commissioning
P. 280

274  Practical Power System and Protective Relays Commissioning































            FIGURE 18.12.3 Delta star power transformer differential protection connections with earth
            fault on the low-voltage side on phase B.



            18.12.6.2 Tap Changers
            Any differential scheme can only be balanced at one point of the tap
            changer, and it is usual to choose CT ratios that match at the midpoint of the
            tap range. Note that this might not necessarily be the normal rated voltage.
            For example, if the tapping range is 110%,  20%, then the CT ratio should
            be based on a current corresponding to the  5% tap. The theoretical maxi-
            mum out of balance in the differential circuit is then 115%.

            18.12.6.3 Auto-Transformer Differential Protection

            Auto-transformers can be adequately protected by high-impedance differen-
            tial relays. The setting voltage is calculated assuming the worst through-
            fault conditions and therefore bias is not necessary. CTs are required on the
            HV, LV, and neutral connections and all must be the same ratio. The CT
            ratio should be based on the LV full load current for the nearest standard
            ratio. This form of protection will not detect interturn faults (refer to
            Fig. 18.12.4).
               The corner of an unloaded delta tertiary winding can be earthed on the
            main transformer earth, thereby including the delta winding within the zone
            of protection. However, the percentage of the delta winding that is protected
   275   276   277   278   279   280   281   282   283   284   285