Page 281 - Practical Power System and Protective Relays Commissioning
P. 281

Protection Relays Chapter | 18  275






















             FIGURE 18.12.4 Auto-transformer differential protection.

             will be minimal due to the high CT ratios that the protection requires. If
             more sensitive earth fault protection is required for the delta winding, a
             separate earth should be used, together with a suitable CT and relay. The
             protection is also stable under over fluxing conditions, and magnetizing
             inrush. If CTs are not available on the neutral, a biased differential relay
             can be used in the conventional way. The line CTs should be connected in
             delta (as for the star/star transformer). The biased differential relay will
             give a measure of interturn protection and will also detect delta tertiary
             faults.


             18.12.6.4 Earthing Transformer Protection

             If the earthing transformer is inside the zone of differential protection then
             no separate protection is required. Overcurrent protection can be provided by
             three overcurrent units connected to delta-connected main CTs, as shown in
             Fig. 18.12.5.
                The protection will not operate on zero-sequence currents due to system
             earth faults because of the CT delta connection.


             18.12.7 ZERO-SEQUENCE CIRCUITS OF TRANSFORMERS

             18.12.7.1 Two-Winding Transformers
             Consider, for example, a two-winding transformers delta/star connection, as
             shown in Fig. 18.12.6.
                The zero-sequence currents will be there in the star connection side of
             the transformer but will not be there in line with the connection of the delta
             side (primary side) of the transformer.
   276   277   278   279   280   281   282   283   284   285   286