Page 276 - Practical Power System and Protective Relays Commissioning
P. 276

270  Practical Power System and Protective Relays Commissioning


               Abnormal operating conditions, such as over voltages, over excitation, or
               overloading;
               Uncleared external faults;
               Transformer connections.

                   Group 1  0 degrees  Phase displacement  Y y0 , D d0 , Z d0
                   Group 2  180 degrees  Phase displacement  Y d6 , D d6 , D z6
                   Group 3  30 degrees  Lag phase displacement  Y d1 , D y1 , Y z1
                   Group 4  30 degrees  Lead phase displacement  Y d11 , D y11 , Y z11

               Differential protection is not enough to protect the transformer against
            earth faults, especially in solid-earthed systems, and there is a need to have
            separate earth fault protection.



            18.12.1.1 Transformer Inrush Current
            When the transformer is first energized a transient current follows, which
            may reach instantaneous peaks of 8 30 times the transformer full load
            current.
               Factors affecting the duration and magnitude of inrush current are as
            follows:

              Size of the transformer bank;
              Size of the power system;
              Resistance in the power system from the source to the transformer bank;
              Residual flux level;
              Type of iron used for the core and its saturation level.
               There are three conditions which can produce a magnetizing inrush
            effect:

            1. First energization;
            2. Voltage recovery following external fault clearance;
            3. Inrush current due to a parallel transformer being energized.
               Inrush current can be detected by the second harmonic contents, which
            are high in inrush current and low in fault current so we can detect the
            second harmonic in inrush current and block the operation of differential
            protection at the starting of transformer energization.
               Another method used to detect the inrush current is the zero detection in
            current waveform as the inrush current has a significant period in each cycle
            where the current is substantially zero, but the fault current passes through
            the zero point very quickly.
   271   272   273   274   275   276   277   278   279   280   281