Page 278 - Practical Power System and Protective Relays Commissioning
P. 278

272  Practical Power System and Protective Relays Commissioning


            18.12.4 TRANSFORMER EARTH FAULT PROTECTION
            Restricted earth fault protection is used to provide instantaneous earth fault
            protection to the transformer, utilizing high-impedance principal. As shown
            in Fig. 18.12.2 below, balanced earth fault for a delta (or unearthed star)
            winding can be provided by connecting three line CTs in parallel (residual
            connection). The relay will only operate for internal earth faults since the
            transformer itself cannot supply zero-sequence current to the system. The
            transformer must obviously be connected to an earth source, as shown in
            Fig. 18.12.2.





















            FIGURE 18.12.2 REF protection for transformers in star connection and balanced EF protec-
            tion for transformers with delta connection.

               On resistance-earthed power systems, unrestricted earth fault protection is
            referred to a standby earth fault protection of two stages of type inverse time
            relay, which match the thermal characteristic of the earthing resistor.
               In practice, two EF relays with stage one set at 15% of full load current
            of transformer with a 5 seconds time delay and the send stage set to 20% of
            full load current of the transformer with an 8 seconds time delay, the first
            stage trips the LVCB and the send stage trips the HVCB.
               Typical settings for REF protection are:

            Solidly earthed    10% 60% of winding rated current
            systems
            Resistance-earthed  10% 25% of minimum earth fault current for fault at
            systems            transformer terminals

            18.12.5 BUCHHOLZ PROTECTION

            All types of fault within a transformer will produce heat, which will cause
            decomposition of the transformer oil. The resulting gases that are formed
            rise to the top of the tank and then to the conservator. A Buchholz relay
   273   274   275   276   277   278   279   280   281   282   283