46  Practical Power System and Protective Relays Commissioning




























            FIGURE 4.12 Induction motor construction.


               For starting the induction motor there are a different methods some of the
            common used one are as follows methods:
            1. Rotor resistance method.
            2. Stator resistance method.
            3. Auto-transformer method.
            4. Star delta method.


            4.10 THE PRE-START COMMISSIONING TESTS OF
            INDUCTION MOTORS

            The following prestart commissioning tests should be undertaken:
             1. Insulation resistance measurement. This test is done by using a Megger
                test of phase-to-earth and phase-to-phase to check the dryness and qual-
                ity of insulation.
             2. Measurement of winding DC resistance, to check the winding and
                circuits.
             3. High voltage tests and insulation tests. This test is done to check the
                quality of insulation.
             4. Phase sequence check
             5. Tests of protective relays. This test is done to check the protective
                relays at the approved setting from the client’s engineers.
             6. Tests of motor auxiliaries and motor cooling system.