Electrical Design Characteristics and Issues     199


                      N
                              φ
                                        Cogeneration tie bus



                              52 Cogen breaker

                                               65
                                               C
                                                             43
                           CT                   52A                    A
                                                                kW/kvar
                                        50                         43
                            3           51  32  65 kWh  40             V
                                                                       F
                               (2)
                                                                       T
                                    PT
                                                  27  81        43
                                                                25
                                    PT
                           CT
                                        90
                            3           C       52A       90

                                                           Field
                                                               To utility
                             GEN                              connection






                          R    Medium voltage
                                2.4 to 15 kV
                         59

        FIGURE 11-2  Typical protection for CHP generator connected to utility–generator section.


                the utility if utility voltage is below nominal, and helps detect issues of islanding,
                voltage regulation malfunction, or faults causing voltage dip. Because system voltage
                transients are normal, this relay usually has a 2-second time delay on drop out and
                a 1-second time delay on pick up. Drop out is typically at 75 to 80 percent and pick
                up at 90 percent of nominal voltage.
                43-Manual selector switch. These are not part of the control system, but rather allow
                for multiple meter readings and are often incorporated directly into digital meters.
                Three manual selector switches are shown in this example: one selects phase for