Page 409 - Sustainable On-Site CHP Systems Design, Construction, and Operations
P. 409

382    Ca s e  S t u d y 5


                The Institute of Electrical and Electronic Engineers prepared a generic, but mathe-
             matically rigorous reliability study of an idealized radial power system that uses actual
             field records of component reliability data gathered by the U.S. Army Corps of Engi-
             neers Power Reliability Enhancement Program. Two radial systems are modeled:

                  1.  The first with CHP run in parallel with a typical macrogrid utility (schematic
                    shown in Fig. 23-3).
                  2.  The second without CHP (schematic not shown, but with the same power chain
                    architecture of Fig. 23-3 without the continuously operating 13.8-kV gas turbine).

                                               13.8 kV

                                              NC
                                                      Utility
                             Short length of cable  Emergency Management
                                                       Facility


                                        NC
                                                182.88 m
                                                 (600 ft)
                                                 cable    NC
                                                                 1000 kVA
                                        NC
                                                                 generator
                                     91.44 m
                                     (300 ft)
                                      cable
                                           182.88 m  (600 ft)  cable


                                              NC
                                            Short length of cable
                                  7,500 kVA
                                               13,800 / 480 V
                                     8%
                                              NC









                             91.44 m  (300 ft)  cable




                                       Critical operation power
                             480 V

             FIGURE 23-3  Simple radial power system with CHP. [Source: IEEE/ANSI 493-2007 (Ref. 13).]
   404   405   406   407   408   409   410   411   412   413   414