Title           Scope or Definition     Fine Print Note
         700             These systems are intended  FPN No. 3: Emergency systems are generally
         Emergency       to automatically supply   installed in places of assembly where
         Systems         illumination, power, or both,  artificial illumination is required for safe
                         to designated areas and   exiting and for panic control in buildings
                         equipment in the event   subject to occupancy by large numbers of
                         of failure of the normal   persons, such as hotels, theaters, sports
                         supply, or in the event of   arenas, health-care facilities, and similar
                         accident to elements of a   institutions. Emergency systems may
                         system intended to supply,   also provide power for such functions as
                         distribute, and control   ventilation where essential to maintain life,
                         power and illumination   fire detection and alarm systems, elevators,
                         essential for safety to   fire pumps, public safety communications
                         human life.             systems, industrial processes where current
                                                 interruption would produce serious life safety
                                                 or health hazards, and similar functions.
         701             These systems are intended  FPN: Legally required standby systems
         Legally Required   to automatically supply   are typically installed to serve loads, such
         Standby Systems  power to selected loads   as heating and refrigeration systems,
                         (other than those classed   communication systems, ventilation and
                         as emergency systems) in   smoke removal systems, sewage disposal,
                         the event of failure of the   lighting systems, and industrial processes,
                         normal source.          that, when stopped during any interruption
                                                 of the normal electricity supply, could create
                                                 hazards or hamper rescue or fire-fighting
                                                 operations.
         702             These systems are intended  FPN: Optional standby systems are typically
         Optional Standby  to supply power to public   installed to provide an alternate source
                         or private facilities or   of electric power for such facilities as
                         property where life safety   industrial and commercial buildings, farms,
                         does not depend on the   and residences and to serve loads such
                         performance of the system.  as heating and refrigeration systems, data
                         Optional standby systems   processing and communications systems,
                         are intended to supply   and industrial processes that, when stopped
                         on-site generated power   during any power outage, could cause
                         to selected loads either   discomfort, serious interruption of the
                         automatically or manually.  process, damage to the product or process,
                                                 or the like.
         708.2           Power systems for facilities  FPN No. 1: Critical operations power systems
         Critical Operations  or parts of facilities   are generally installed in vital infrastructure
         Power Systems   that require continuous   facilities that, if destroyed or incapacitated
         (COPS)          operation for the reasons   would disrupt national security, the economy,
                         of public safety, emergency   public health or safety; and where enhanced
                         management, national    electrical infrastructure for continuity of
                         security, or business   operation has been deemed necessary by
                         continuity. (Emphasis   governmental authority.
                         added.)