Page 95 - Sustainable On-Site CHP Systems Design, Construction, and Operations
P. 95

Thermal Design for CHP     73



        Thermal Technologies
             For many CHP designs, there is a need to provide some form of thermal energy other
             than heating, in order to maintain high annual load factor or to meet process needs. For
             the purposes of this discussion, thermal technologies are considered to be devices that
             are driven by heat and used to provide some form of useful thermal energy other than
             heat. Thermal technologies generally use the products of the heat recovery system but
             in some cases they can use the thermal energy generated by the prime mover directly
             and thereby combining the heat recovery function into the thermal technology. These
             thermal technologies can be broken into various equipment groups as follows:

                 •  Absorption chillers
                 •  Adsorption chillers
                 •  Steam turbine–driven chillers
                 •  Desiccant dehumidifiers

             We will review each of these technologies briefly with respect to their applicability to
             CHP design. Further information on the operation and particular characteristics for
             each technology is available from a variety of sources.

             Absorption Chillers
             There are multiple forms of absorption chillers available using a variety of refrigerants
             and configurations. In order to understand the basics we will take the most common
             form of absorber available—the hot water–fired single-stage lithium bromide absorption
             (LiBr) chiller.
                The operating principle is based on the relationship between the absolute pres-
             sure and boiling point of water. At atmospheric pressure (14.7 psia) pure water boils
             at 212°F. As the pressure increases the boiling point is raised and as the pressure
             reduces the boiling point is lowered. In a LiBr absorber, water is used as the refrigerant
             and is sprayed on the tube bundles which contain building chilled water at 54°F, for
             example. The absolute pressure in the absorbers evaporator section is reduced to
             approximately 0.1 psia. At this pressure, water will boil at approximately 40°F. The
             building chilled water inside the evaporator tubes provides sufficient heat to cause
             the refrigerant water to boil. This change in phase of the refrigerant requires energy
             which is supplied by the building chilled water. The energy given up by the building
             chilled water is in the form of sensible energy resulting in a drop in temperature, thus
             providing a cooling effect.
                A water/lithium bromide solution is used in conjunction with the refrigerant
             water due to its hygroscopic properties and high boiling point. Once the refrigerant
             vaporizes to cause the cooling effect it will begin to increase the pressure within the
             system and must be removed in order to continue the process. LiBr is sprayed in the
             “absorber section” of the chiller (hence the name) where it absorbs the refrigerant
             (water) vapor to prevent an increase in pressure. The resultant dilute (or weak) LiBr
             is then directed to the chiller’s generator section where the weak solution is heated
             using thermal energy such as hot water. The absolute pressure in the generator is
             considerably higher than in the evaporator to increase the boiling point and
             allow higher temperatures in this area. The water vapor is driven off to regenerate or
   90   91   92   93   94   95   96   97   98   99   100