Page 136 - Uninterruptible Power Supplies
P. 136

Harmonic Distortion of the Supply
            134   Chapter Four


            lowest forcing frequency (which will be equal to the rectifier pulse
            number).


            Effect on Electronic Devices
            A local generator is likely to incorporate electronic devices such as a
            tachometer and a voltage regulator which may use the zero voltage cross-
            ing points as timing signals. Deep notching of the supply voltage can lead
            to additional zero crossings and can affect the operation of such devices.
            If problems are experienced it may be possible to obtain a clean supply by
            using a small low-pass filter.
              Voltage regulators may be affected by a distorted supply; if the regu-
            lator is expected to control the fundamental component of voltage, the
            harmonic voltages must be removed from the sensing signal and a low-
            pass filter may achieve this as suggested in the previous paragraph. If
            the harmonic voltages are not removed the regulator will set to the true
            rms or the average value depending on the design. In cases of severe
            distortion this can lead to considerable errors.


            Reduction of Distortion Due to
            Rectifier Loads

            Increasing the Pulse Number
            In the section titled “Harmonics Generated by Bridge Rectifiers” it is
            stated that the current taken by a three-phase six-pulse bridge rectifier
            includes only the fifth and seventh, eleventh and thirteenth, seventeenth
            and nineteenth, etc., harmonics. If the rectifier pulse number is increased
            to 12, the fifth and seventh, seventeenth and nineteenth, etc., are can-
            celed while the magnitudes of the remaining harmonics are unaltered. To
            comply with the planning levels of Engineering Recommendation G.5/4 it
            is often necessary to use 12-pulse rectifiers.
              For the same reason the supplies to rectifiers of multiunit UPS
            installations should be phase shifted, to achieve a higher pulse number.
            The supplies to two paralleled units should be shifted by 30°, three
            units by 20°, etc. For a phase-shifted multiunit redundant system, the
            loss of a unit will result in some additional harmonic currents being
            drawn from the system.
              The manner in which this harmonic cancellation occurs is not obvious
            and the reader may wish to study Table 4.3 which is an attempt to explain
            how it is achieved, it is not offered as a rigorous mathematical exercise.
              It can be seen that for both fifth and seventh harmonics the two sec-
            ondary currents have a phase difference of 180°. It follows that they
            will be cancelled in the primary; similar reasoning may be applied to
            the seventeenth and nineteenth harmonics.



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   131   132   133   134   135   136   137   138   139   140   141