Page 131 - Uninterruptible Power Supplies
P. 131

Harmonic Distortion of the Supply
                                             Harmonic Distortion of the Supply  129


              sumers. The point of common coupling will be regarded as the point
              of supply (the consumer’s terminals).
            ■ The consumer is supplied at low voltage by a dedicated cable from a
              nearby substation. The point of common coupling will be regarded as
              the substation low-voltage busbars.
            ■ The consumer is supplied at high voltage and owns high-voltage
              switchgear, one or more transformers, and high- and low-voltage dis-
              tribution systems as appropriate. The point of common coupling will
              be regarded as the high-voltage intake terminals.

              The third pattern of distribution in which power is taken at high volt-
            age is worthy of comment. The high-voltage network is likely to have a
            low impedance and the network operator will allow a large harmonic
            load to be connected to it, much larger than would be allowed if the
            point of common coupling was on the low-voltage side. If a large dis-
            torting load is connected to the low-voltage system the entire con-
            sumer’s low-voltage system will be heavily distorted and damage and
            malfunction may result. As the point of common coupling is on the
            high-voltage side the network operator is neither responsible for nor
            concerned with distortion on the low-voltage side; any corrective action
            required will be the responsibility of the consumer.
              If nonlinear equipment is to be installed within such a system the
            problem can be avoided by stating, within the contract documents, that
            Engineering Recommendation G.5/4 applies and the point of common
            coupling is to be regarded as the equipment terminals or some other
            clearly defined point within the low-voltage system.


            The Effect of Bridge Rectifier Loads on Local
            Generators
            Impedance of the Supply
            If the electricity supply is derived from a local generator, all the effects
            mentioned in the previous section may be experienced but, as the
            source impedance will almost certainly be higher than that of a supply
            system, the effects are more likely to be troublesome. There are other
            additional effects which occur owing to the nature of synchronous
            machines, and these are described in subsequent paragraphs.
              The magnitude of the effects described in this section depend on the
            rating of the local generator. If a rectifier is supplied from a very large
            generator the effects will be negligible and the supply may be regarded
            as a low-impedance system as considered in the previous section.
            However, many standby generating sets supply uninterruptible power
            supplies which have rectifiers as their input modules and the effects
            may well become relevant.


         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   126   127   128   129   130   131   132   133   134   135   136