Page 234 - Uninterruptible Power Supplies
P. 234

Notes on Systems Installation
            232   Chapter Nine


              Consideration should also be taken of the well-known fact that pre-
            dicted loads have a habit of increasing, when it is evident that a high
            security power supply is envisaged for a stated location.
              Clearly consideration should be given as to the type of UPS system
            to be employed, static or rotary and which circuit is most suitable. As a
            guide, rotary sets these days are of higher reliability but at a signifi-
            cantly higher cost. Static systems certainly are almost universally in
            use up to about 50 kVA, and gradually beyond this rating rotary sets
            should be given consideration. Price and reliability have to be balanced
            for the project in hand.
              Assuming that the UPS power rating has been ascertained, attention
            may now be given to the rating of the generator (usually a diesel gen-
            erator set). Thus, consideration should be given to the following:
              Computer rating and possible waveform problems
              Air conditioning and variations in load due to operational requirements
              Emergency lighting: there may be two sections, one portion directly
              from the UPS and (with a delay in operation) from the generator
              Security systems

            There may be other loads to consider depending on site conditions.
              The generator will usually assume loads in the following way: ini-
            tially air conditioning, lighting, and security. Note that it may be advis-
            able to switch these loads on with small delays using a delay timer
            system to avoid heavy surge loads onto the prime mover. In most
            instances the UPS is the last load to be presented to the prime mover
            as it will be working from the battery system. The UPS also has a load
            ramp-up feature which allows a relatively slow rise in power demand
            from the UPS.
              It should be remembered that the power demand from the UPS will
            consist of three sections: UPS load, losses in the UPS system, and
            recharging the battery. This extra load, present when recharging the
            battery, may be deferred until the system is restored to mains opera-
            tion, but this deferment of battery recharge does have the penalty that
            a second outage of mains power soon after mains restoration may
            result in a complete loss of UPS power due to a battery incapable of
            supplying sufficient power.
              Care should be taken to ensure that any harmonics induced onto the
            prime mover are taken into consideration. As stated in previous chap-
            ters harmonics induced onto the mains or the prime mover from the
            UPS will vary with UPS design. If, for example, a fifth harmonic filter
            is employed on the input to the UPS, low load conditions and variations
            in frequency from the prime mover may have a detrimental effect.



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   229   230   231   232   233   234   235   236   237   238   239