Page 237 - Uninterruptible Power Supplies
P. 237

Notes on Systems Installation
                                                Notes on Systems Installation  235


              If there is a remote radiator, warm air will be discharged from it and
              it will be an additional source of noise
              Vibration should be considered if the generating set is within an
              occupied building, steel framed buildings are particularly suscepti-
              ble to noise generated by rotating sets
              Leakage of fuel, fuel tanks are frequently required to be bunded
              The generating set should be close to its electrical load and as close
              as practicable to a supply of fuel
              An expansion of generator installation guidelines can be obtained in
            Chap. 1.
              The chances of a prime mover failure are remote these days. For
            example, in lieu of batteries we now have a flywheel design which
            requires the prime mover to provide full power in approximately 12 to
            15 s. Or indeed the close coupled diesel sets are able to support the sys-
            tem within 2 to 3 s!
              The project may require consideration of local government authority,
            as regards the effect of appearance, noise, exhaust fumes, and of course
            local fire regulations. Consideration will also have to be given to mains
            power.
              Adequate space for the system will require consideration to allow ser-
            vicing of the equipment. It should be noted that in the case of most cubi-
            cles (either rotary or static UPS) rear access for servicing is required.
            Access to wound components such as transformers is often given a low
            access priority on the supposition that failure rate of such devices is low.
              Since the devices are heat generating, adequate ventilation must be
            provided. For example, a static UPS rating 200 kVA will be a fan cooled
            cubicle generating some 16 kW of heat at full load. The UPS itself can
            work in ambient temperatures up to 40°C. However, the supporting bat-
            tery, particularly those of a VRLA design, is best operated at 20 to 25°C
            (68 to 77°F). When designing battery stands or enclosures ensure that
            cooling air is allowed to surround the cell by allowing a gap of 10 mm
            between cells. Heat build up in such enclosures can be a major defect.
            Typically, an enclosure will allow a 2 degree ambient temperature rise.
              The design of small UPS modules where space is at a minimum can
            have a major effect on battery performance. Also, ensure that for such
            small units operational staff refrain from locating the device adjacent
            to a heat source such as a radiator, and that the usual warning lamp of
            low battery is visible!
              It is surprising how many instances we have found of the small UPS
            being installed in unfavorable conditions, and then forgotten! There is
            a tendency for such units to be treated as another black box, just





         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   232   233   234   235   236   237   238   239   240   241   242