Page 235 - Uninterruptible Power Supplies
P. 235

Notes on Systems Installation
                                                Notes on Systems Installation  233


            Under certain adverse conditions, such filters will exacerbate the wave-
            form problem.
              The static UPS system may be classed as a comparatively high
            impedance power source and thus adequate sub-subject protection
            should be allowed for, usually in the form of high speed fuses or circuit
            breakers. The many designs of rotary systems may have up to 14 to 15
            times FLC to allow for subcircuit protection, so the problem is some-
            what eased.
              The autonomy period of the battery will have to be considered. As a
            guide most systems have 10-, 15-, or 30-min autonomy but there are
            some notable exceptions. Oil/chemical production, power generation,
            communications, and defense systems may have very long autonomy
            periods even up to 12 to 24 h, but these are the exceptions. The choice
            of 10 to 15 min autonomy has been made from the following considera-
            tions: It was considered feasible to shut down the computer in an
            orderly fashion if the prime mover failed to provide power. Since it will
            take at least 20 to 30 s for the detection of prime mover failure, is there
            sufficient time to react to such a condition and then perform an orderly
            shut down?
              The alternative of employing wet cells should be envisaged and the
            following points should be taken into account. Stands, usually of steel
            construction these days, should be provided with a heavy plastic
            sheathing or a high-quality paint to inhibit chemical attack. The bat-
            tery isolator should be immediately adjacent to the battery stand as
            cable from the isolator to the actual battery is clearly unprotected.
            Battery terminals are to be insulated usually with a close-fitting plas-
            tic cap. If cells are to be operated at relatively high ambient tempera-
            tures say above 30°C then the specific gravity of the electrolyte in the
            cells should be reduced (refer to the manufacturer).
              Clearly, such cells will evolve gas when charging, in particular hydro-
            gen, and a 4 percent admixture of hydrogen with air is an explosive con-
            dition. Most advice is to ensure that the maximum hydrogen content in
            the environment is no greater than 1 percent. The production of hydro-
            gen is basically a function of plate area, and charging current.
              A simple formula to calculate gas emission is as follows:

              Number of cells   charging current   0.0004194   cubic meters.
            Knowing the overall volume of the room, it is then easy to calculate the
            number of air changes per hour to ensure a low concentration of hydro-
            gen gas. Such ventilation should preferably be by fans employing
            flameproof motors. The room should use flooring capable of withstand-
            ing acids, walls should be painted in a corrosion-proof light-colored
            paint, and lighting fixtures should be vapor proof.



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   230   231   232   233   234   235   236   237   238   239   240