Page 93 - Uninterruptible Power Supplies
P. 93

Additional Information Relating to the Standby Supply Installation
                      Additional Information Relating to the Standby Supply Installation  91


              The generator must be capable of supplying the total required elec-
            trical load to the distribution system. This will be equal to the power
            rating of the engine as derived above less the losses within the genera-
            tor (5 or 6 percent).
              While the basic engine rating is expressed in kWm the basic genera-
            tor rating is in kVA, which is the phasor sum of kWe and kVAr. The
            relationship is defined by the well-known equations:

                                    kW   kVA   cos                      (3.1)

            and                    kVAr   kVA   sin                     (3.2)


            The Effect of UPS Loads on the Generator
            kVA Rating
            Most standby power generators provide power to one or more uninter-
            ruptible power supply systems which may use six-pulse rectifiers as
            their input modules. As described in Chap. 4, a six-pulse rectifier gen-
            erates harmonic currents of the orders 5, 7, 11, 13, etc., the theoretical
            total harmonic distortion being 30 percent. In practice it is usually
            higher. In passing through the generator these harmonic currents will
            cause voltage distortion which is undesirable for many reasons. If the
            total harmonic distortion of the generator voltage is to be limited to say,
            10 percent, the total six-pulse rectifier load on a generator should not
            exceed 30 or 40 percent of its kVA rating, depending on whether it has
            high or low subtransient reactance. A precise calculation requires the
            use of data which will be available to the generator manufacturer.

            The Step Loading Ability of the Generator
            Generators experience no difficulty in accepting step loads up to 100
            percent or more of their rating. The resulting transient voltage drop,
            however, has to be considered as it must be within the limits defined by
            the voltage performance class (G1, G2, G3, or G4).
              When load is applied to a generator, there is an immediate drop in out-
            put voltage due to the stator subtransient reactance (X″) and resistance
            (R). The voltage regulator will respond quickly, but the exciter and rotor
            fields are highly inductive and, owing to their time constants, there is
            delay in increasing the excitation of the machine. The generator rotor
            will also suffer a loss of speed which will further reduce the voltage. For
            self-excited machines (in which the exciter field is energized from the
            generator output) the voltage drop at the generator terminals is trans-
            ferred to the exciter field, still further increasing the drop. It is likely
            that the output voltage drop will be increased by armature reaction




         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   88   89   90   91   92   93   94   95   96   97   98