Page 98 - Uninterruptible Power Supplies
P. 98

Additional Information Relating to the Standby Supply Installation
            96   Chapter Three


            cumulative load seen by the generator is 466 kWe when motor A is
            accelerating, which will require 496 kWm from the engine. It follows
            that the maximum or prime power required from the engine will be 496
            kWm, and the continuous power will be 405 kWm, or 81.6 percent of
            the maximum. The average power over a 24-h period will depend on the
            duration of the initial sequence and will be a little over 81.6 percent.
              The maximum step load applied to the generator is 240 kWe which
            will require 255 kWm from the engine. This is 51.5 percent of the max-
            imum rating, an acceptable figure since most engines will accept a
            60-percent step load.
              For some applications a simpler table will suffice. Table 3.1 includes
            some redundant information, which may, however, be useful as it assists
            in checking the arithmetic used in compiling the table. The full informa-
            tion also enables the reader to see all the changes that occur during the
            loading sequence.
              Unless a safety margin has been allowed in the loads given, it would
            be wise to increase these ratings by say 10 percent. ISO 8528 does not
            allow for any overload rating, whereas ISO 3046 requires engines to be
            capable of supplying 10 percent overload for 1 h.

            The Generator Rating
              The continuous load is 457 kVA.
              The maximum step load is 597 kVA when motor B is started.
              If a generator rated at 500 kVA is used the volt drop on application of
              motor B would be:
                            Drop   (597   500)   11%   13.2%

              To restrict the volt drop to 12 percent would require a rating of:

                               500   13.2   12   550 kVA
              The preceding calculations are an estimating procedure which will
            give approximate results. The generating set manufacturer, in consul-
            tation with the engine and generator manufacturers, will usually be in
            the best position to make the final decisions.

            Reliability and Redundancy
            Reliability
            The reliability of a standby power supply will depend on a number of
            factors such as:
              The design of the equipment that has been installed



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   93   94   95   96   97   98   99   100   101   102   103