Page 268 - Valve Selection Handbook
P. 268

Rupture Discs                      255


            If  vented  equipment  must be  located  within buildings,  it  should  be
          located  close  to  exterior  walls  so that the  vent ducts will be  as  short  as
          possible,  preferably no more than 3m long. 1
            In  the  case  of dust explosions  hazard  class  KST  up  to  250  bar  x  m/s,
          flame  propagation  can  be  prevented  altogether  by  combining  the  vent
          panel  with a  tube-shaped  flame  trap  or  flame-quenching  vent  system as
          shown in Figure  6-38.  By this construction,  gases  entering  the flame trap
          with a temperature of up to  1500°C (2700°F) leave the flame trap with a
          temperature  of  less  than  100°C  (210°F).  This  temperature  drop  reduces
          the escaping gas volume by a factor  of approximately  10, compared with
          unrestrained venting. All  solids  are retained  by an integrated ceramic fil-
          ter mat within the tube.
            This  construction  allows  explosion  venting  to  be  carried  out within
          closed  rooms.  Passages  past  the  flame  trap  need  only  to  be  shielded
          against surprise  effect.








































          NFPA68 (1988), Guide for  Venting  of  Deflagrations  (5-4.4, Effects  of Vent Ducts)
   263   264   265   266   267   268   269   270   271   272   273