136 Advanced Design Examples of Seismic Retrofit of Structures
FIG. 3.10 Column C-S-1.
3.3.2 Quantitative Evaluation of the Overall Performance
of the Building
3.3.2.1 Lateral Displacements
The lateral displacements of stories of two loading directions under a critical
loading combination (presented in Section 3.5.1.3) are shown in Fig. 3.15 for
the northern and southern parts of the building. As can be seen in this figure,
for the North-South loading direction, the lateral displacement of the 7th story
in the southern and the northern parts of the building is 24cm and 37cm,