Page 194 - Boiler_Operators_Handbook,_Second_Edition
P. 194

Refrigeration & AC                                                                                  179

               atmospheric temperature is colder, fan speed is adjusted  cilities that only receive heating and ventilation. Since
               to maintain a minimum temperature, unlike the typical  most people today expect complete air conditioning it’s
               water-cooled condenser where water flow is controlled.  not necessarily an applicable label anymore. Air condi-
               Variable speed drives on cooling tower water pumps  tioning is the best overall label.
               can reduce power costs but are limited to ensure good     While they’re not as common as they used to be
               distribution of the water in the cooling tower.      the typical window unit (Figure 5-40), is a packaged air
                    The water vaporized in a cooling tower has to be  conditioning system that incorporates a complete refrig-
               replaced with makeup. In addition, because the vapor  eration cycle within it to transfer heat from the room to
               doesn’t  carry  off  the  solids  that  were  dissolved  in  it,  the atmosphere outside the window, is still familiar to
               blowdown of the cooling tower is required to prevent  most of us. Air from the room (A) is drawn into the unit
               scaling  and  deposits  of  mud  on  the  fill.  Small  towers  through a filter (B) that cleans the air, the air passes over
               commonly  have  a  float  valve  in  the  sump  that  adds  an evaporator coil (C) with fins that removes the heat
               makeup water to maintain the level. Larger towers can  from the air and condenses some of the moisture in the
               have level controls using an electric probe system that  air then a fan (D) blows the air back into the room (E) at
               senses the water level to open and close a solenoid or  a high velocity so that it mixes with the rest of the room
               motorized makeup water valve. Blowdown control can  air to produce the comfortable condition. To achieve all
               be manually set or automatic and except for cooling the  the requirements for air conditioning there’s usually a
               water they work the same as a boiler’s continuous blow-  small damper (F) in the barrier between the indoor and
               down. Any large system will also have meters on the  outdoor air that can be opened to admit outside air into
               makeup and blowdown water flows to produce a dif-    the flow of room air to be conditioned to achieve ven-
               ference between the two that equals water lost to vapor-  tilation. Condensate which is moisture removed from
               ization and drift so the owner doesn’t pay to for sewage  the room air drips (G) into a drain pan at the bottom
               treatment of water that wasn’t dumped down the sewer.  of the unit and passes through a trap (H) formed in the
                    Just like a boiler the cooling tower water chemistry  bottom of the casing to the outdoor side of the unit. A
               has to be monitored and maintained to prevent damage  slinging ring attached to the outside of the condenser
               to the tower, the condenser, the pumps, and piping. In  fan (I) picks up the condensate and hurls it at the con-
               addition to scale and corrosion protection chemicals are  denser (J). Heat from cooling the air and condensing the
               added to control the growth of bacteria and algae in the  moisture is absorbed by the refrigerant with flow into
               cooling tower water.                                 the evaporator controlled by a metering device, in Fig-
                                                                    ure 5-40 a capillary (K) and, for the typical window unit
                                                                    with R-134a into the evaporator (C) at a pressure of 35
               AIR CONDITIONING                                     psig which corresponds to a saturation temperature of
                                                                    40°F. The boiling refrigerant absorbs the heat from the
                    Normally we think of air conditioning as cooling  room air and condenses some of the moisture from the
               the air in a space, a room, or building. More appropri-  room air to cool it from a design room temperature of
               ately air conditioning should be considered to be the  75°F to approximately 55°F. Once all the refrigerant has
               heating or cooling plus adding or removing moisture  evaporated (L) the gas is heated to a leaving tempera-
               and removing airborne contaminants from the space to  ture of 50 to 60°F (10 to 20 degrees of superheat). The
               maintain conditions in that space that are comfortable  refrigerant passes through the insulated barrier between
               for  the  occupants.  That  definition  covers  more  than  the room and outdoors to the inlet of the compressor
               what we typically think of. In many zoos around the  (M). The gas is compressed by the compressor to a pres-
               country  there are spaces where  the conditions are  not  sure of 100 psig raising the temperature of the gas that
               necessarily comfortable for humans but are enjoyed by  enters the condenser to 200°F. The condenser (O) trans-
               the occupants. With few exceptions air conditioning is  fers the heat removed from the room along with the heat
               accomplished by removing air from the space, altering  added by the compressor to outside air drawn into the
               its conditions, then returning it to the space where it is  outside casing by the condenser fan (I) through louvers
               mixed with the air in the space to produce the comfort-  in the side (P), passing over the condenser and out grills
               able conditions for the occupants.                   (Q) at the back and top of the unit. The grill at the top of
                    Another term you should hear is HVAC, standing  the unit permits admission of rain water that can assist
               for heating, ventilating, and air conditioning. I would  in cooling when the moisture contributed to the room
               dissuade the use of the term if it were not for many fa-  air by the moisture from the rain penetrating the room
   189   190   191   192   193   194   195   196   197   198   199