Page 202 - Boiler_Operators_Handbook,_Second_Edition
P. 202

Refrigeration & AC                                                                                  187

               Heating Coil                                         conditions at the outlet of the cooling coil to the appa-
                    Some apparatus, but not all, will have a  heating  ratus outlet conditions, after the heating coil. A typical
               coil after the cooling coil. When cooling of the air isn’t  heating application is shown in Figure 5-45.
               required heating may be and the coil is there to heat the
               supply air leaving the apparatus. It becomes necessary  Humidifier
               in many installations because of the large, required,     Whenever a considerable amount of outdoor air is
               quantity of ventilating air adds so much cold outside  used for ventilation it has to be heated when the outside
               air that heating it is necessary. Even systems with reheat  air is cold and, because the heating increases the dry
               coils (heating coils in the ductwork supplying different  bulb temperature (as indicated by a horizontal line from
               portions of the air conditioned space) will have a heat-  left to right on the psychrometric chart) the humidity of
               ing coil in the main apparatus because the cold air in  that air drops. Unless moisture is added to the air the
               the ductwork would promote condensation that could  personnel in the conditioned space will experience elec-
               damage the insulation and ductwork. The clue here is  tric shocks and other unpleasant conditions.  Humid-
               don’t shut down that heating coil in the winter, nor ig-  ifiers add moisture to the air and, depending on their
               nore it’s lack of operation, thinking the reheat coils will  source of water, can also heat or cool the air.
               take care of things because wet and falling ceiling tiles     The  typical  home  humidifier  consists  of  a  high
               could be the last thing you remember of that particular  pressure spray that atomizes water to form fine droplets
               facility. Heating can be performed with electric heating  of it and inject them into the air stream coming off the
               coils (very expensive to operate), steam or hot water  heater. Others use a ceramic or fiber wick that’s soaked
               heating coils, or a gas or oil fired furnace. Of course the  with water and exposed to the air stream. Some of the
               furnace is not a heating coil but it accomplishes the same  heat in the air is used to evaporate the water. Being a
               purpose and furnaces are discussed later.            boiler operator you know how much heat it takes to con-
                    When there is a heating coil it can be used for par-  vert liquid water to a gas so you can see how the line on
               tial reheat or simply heating. The apparatus can be op-  a psychrometric chart for that service would be drawn
               erated for humidity control of the conditioned space by  from the conditions at the outlet of the heating coil up
               cooling the air more than necessary for temperature con-  and to the left, both adding moisture to the air and cool-
               trol, in order to remove more moisture from the air, and  ing it some.
               reheat it to provide the desired supply air temperature.     Larger applications can use similar means of hu-
                    When simply heating the line representing the  midification but typically use steam humidifiers which
               changing condition of the air on the psychrometric chart  not only add moisture but add heat to the air and the
               is represented by a line drawn horizontally from the ap-  line on the psychrometric chart for that service would
               paratus entering conditions to the apparatus outlet con-  be drawn from the conditions at the outlet of the heat-
               ditions. In reheat applications the line is drawn from the  ing coil up and to the left, both adding moisture to the
                                                                                       air and heating it some. They two
                                                                                       methods are shown on the chart in
                                                                                       figure 5-45. The dashed line shows
                                                                                       that  the  air  coming  off  the  coil
                                                                                       would have to be much hotter to
                                                                                       vaporize the spray or wicked wa-
                                                                                       ter because of the heat necessary
                                                                                       to  vaporize  the  water.  The  steam
                                                                                       only adds about one degree to the
                                                                                       air temperature while cooling the
                                                                                       steam which is already vaporized.
                                                                                         One interesting element of the
                                                                                       diagram on that chart is that the
                                                                                       line for mixing the outside and
                                                                                       return air indicates that, if more
                                                                                       outside air was in the mix, the con-
                                                                                       ditions would be to the left of the
                      Figure 5-45. Psychrometric chart, heating and humidification
                                                                                       saturation curve. That’s when the
   197   198   199   200   201   202   203   204   205   206   207