Page 205 - Boiler_Operators_Handbook,_Second_Edition
P. 205

190                                                                               Boiler Operator’s Handbook

               Ductwork
                    Every system other than window units  and the
               thru-the-wall units at hotels and motels are fitted with
               ductwork to convey the conditioned supply air from the
               apparatus to the air conditioned spaces, return air from
               the conditioned spaces, and supply outside air to the
               inlet of the mixing box on the apparatus. As a general
               rule air leaks in ductwork were typically in the range of
               20% to 30%. Jointing methods for sheet metal duct were
               developed for low cost installation and, except where
               specified  otherwise,  subject  to  sloppy  installation  that
               produced lots of leaks. Even insulated ducts had heavy
               leakage; I can recall looking into a ceiling space to see
               the insulation ballooning around the ducts because of
               the air leaking out of the ducts and pieces of duct tape
               flapping  around  in  the  breeze  where  the  air  came  out
               of the insulation. Newer standards have reduced the
                                                                      Figure 5-46. Duct velocity and regain calculation
               amount of duct leakage but don’t forget that it’s signifi-
               cant in anything designed or built before 1973 when we
               had the first so-called energy crisis.               area can be empty with a large number of people gath-
                    Ductwork is designed one of two ways, constant  ered in one part of the space to produce a concentrated
               friction or static regain. The first is simply choosing duct  load in one section. To handle situations where that can
               sizes so the pressure drop is a constant (0.1 inches W.C.  occur spaces served by a common piece of apparatus
               per 100 feet of duct) so the required discharge pressure  can be fitted with reheat coils that warm the air enter-
               at the supply air fan could be calculated readily by mul-  ing spaces where the cooling load is lower than normal
               tiplying the length of duct (in feet) to the furthest reg-  (no people, sometimes no lights). Conference rooms and
               ister  with  corrections  for  elbows  and  other  fittings  by  similar locations may also have time controls or occu-
               0.001). Static regain design allowed for determination  pancy sensors that actually reset the thermostatic con-
               of the recovery of static pressure as the air velocity de-  trol to allow the room to be cooler, or warmer, unless in
               creases providing additional force to convey the air to  use or scheduled to be in use.
               that furthest register. Regardless of the design the oper-     Reheat  coils  are  typically  thermostatically  con-
               ator only has to know that a boost in static pressure will  trolled for the space in which they are located (which
               occur when the air slows down, provided that it slows  can be part of a number of spaces served by the same ap-
               down in a manner that’s not produced by a damper or  paratus and reheat coil). The control system commonly
               other restriction where the regain is considerably less  uses a method of detecting the warmest of those spaces
               than 100%. The example in Figure 5-46 shows how stat-  to control the temperature of the air leaving the appara-
               ic pressure may be recovered from velocity regain in a  tus and allows the remaining spaces to use their reheat
               duct expansion. Different configurations provide other  coils to achieve comfort in them.
               values for the regain factor (R) but simply looking at a     It seems strange to cool the air then heat it again
               configuration and how abrupt changes are can give you  but it’s one way of ensuring occupant comfort. One chief
               an idea of how much of the potential regain can be re-  operating engineer at a major college told me he could
               covered.                                             count on a considerable decrease in steam load when the
                    Don’t confuse a lack of air flow to a conditioned  chiller plant was shut down for maintenance. To elimi-
               space with blockage of ductwork. I’ve encountered sev-  nate the energy waste associated with reheat some new
               eral problems with duct failures, many including that  system designs, including VAV boxes, have been devel-
               flexible duct which is easy to crush.                oped.

               Reheat Coils                                         VAV Systems
                    When apparatus serves spaces containing many        Most modern systems have air handling units or
               rooms, offices, or cubicles, it’s difficult to ensure occu-  rooftop units with a variable speed drive controlling
               pant comfort because the loads can change. Some of the  the fan to supply conditioned air to VAV boxes. VAV
   200   201   202   203   204   205   206   207   208   209   210