Page 204 - Boiler_Operators_Handbook,_Second_Edition
P. 204

Refrigeration & AC                                                                                  189

               HEPA Filters                                         on the exhaust air to protect the wheel) and they’re fre-
                    A final element added to some systems where the  quently equipped with a number of pressure sensors to
               air quality is critical are HEPA (high efficiency particu-  detect problems of leakage and blockage.
               late arresting) filters and they’re normally installed on
               the outlet of the air handling unit. Since it’s on the pres-  Complete Your Design Charts
               sure side it ensures there will be no infiltration of air after     The last line to draw on your psychrometric chart
               the HEPA filter. The pressure drop required to achieve  is from the equipment outlet condition to the room con-
               the filtration would be added to the negative pressure in  dition and that represents the heat and moisture added
               the apparatus casing which would make in-leakage of  to the air as it enters the room and mixes with the room
               unconditioned air more of a problem along with requir-  air to absorb the heat and moisture that’s generated in
               ing a stronger casing. I know I mentioned the synthetic  the space. Once you have charts for all the design con-
               fiber factory and HEPA filters were used there to prevent  ditions you can use copies of them to compare to actual
               dust particles binding to the fiber during stretching and  operation when problems arise. If you take actual mea-
               spinning  because  that  would  cause  the  fiber  to  break.  surements under full load conditions save those charts as
               HEPA filters can actually be so fine that they can remove  well because they’re “as-builts” not design situations and
               odors. It’s another thing that requires attention to the  a better reference to use. The problem is that we seldom
               instruction manual.                                  reach actual design conditions and have the time to take
                                                                    the readings at exactly that moment. Don’t forget that you
               Heat Exchangers, Heat and Energy Wheels              have at least two design conditions, summer and winter.
                    Applications that require very high percentages of     Now you have something like a steam cycle or re-
               outside air are frequently equipped with some means  frigerant cycle only it’s an air cycle. Label the chart with
               of exchanging some energy between the outside air and  the equipment name or number, copy it and put it away
               exhaust air. Heat pipes were mentioned earlier. Dilution  for the day when you’ll need it. Do a couple of others
               of pollution of the conditioned space by manufacturing  where conditions are different so you get a feel for what
               processes and concern for cross contamination of work  happens there and gradually build your library of the
               are typical situations where 100% outside air is used. I’ll  design and normal operating conditions for each piece
               resist commenting on the former but I did have the op-  of air conditioning equipment so you have the informa-
               portunity to design air conditioning for a forensics lab-  tion you need at hand and fully understand what’s sup-
               oratory where contamination of samples was a concern  posed to happen.
               and they used 100% outside air. My design incorporat-
               ed a simple heat exchanger that kept the two airstreams  Air Handling Units
               isolated and ensure no cross-contamination.              The typical AHU consists of a mixing box where
                    Heat and Energy Wheels are what the name im-    return and outside air are mixed before entering the fil-
               plies. The heat wheels contain a fine lattice of metal that  ters, a filter box, face and bypass dampers (if included),
               absorbs heat from the hot air in summer and dumps it  an access space for maintenance of the cooling coil, cool-
               into the cooler exhaust air then absorbs heat from the  ing coil, another access space for both cooling and heat-
               exhaust air in winter and heats the cold outside air. En-  ing coils, heating coil, humidifier, and fan housing. Most
               ergy wheels, sometimes called enthalpy wheels, use a  AHUs are fitted with a fan driven by a shaft connecting
               desiccant coating that allows the wheel to absorb and  to a sheave outside the unit with the motor, sheave, and
               discharge moisture as well. The wheel is installed in  belts. These are typically prefabricated in sections for
               a casing with outside and exhaust air inlet and outlet  field assembly but can also be shipped as an assembled
               connections so as it rotates it picks up heat (and mois-  unit that is simply rigged into place. Most AHUs use
               ture) from one air stream and discharges it to the other.  chilled water in the cooling coil and steam or hot wa-
               I believe you can tell that this application doesn’t dif-  ter in the heating coil. Valves controlling the flow of the
               ferentiate between heat and moisture and other things  heating and cooling mediums have to be added along
               that can be in the air so it’s possible that contamination  with diffusers, supply, return, and outside air ductwork
               from the conditioned space can be returned to the out-  to complete the installation. Openings for access to in-
               side air drawn into the unit. A particular problem with  spect and maintain the filters, fan and coils are provided
               the wheel units is maintaining the seals that separate the  in the casing. A drain pan is provided at the bottom of a
               two air streams. Secondary problems include blockage  cooling coil to collect and direct the condensate formed
               due to filter leakage (yes, some of them require filters  as moisture is removed from the air.
   199   200   201   202   203   204   205   206   207   208   209