Page 208 - Boiler_Operators_Handbook,_Second_Edition
P. 208

Refrigeration & AC                                                                                  193

               its performance. I don’t think that it’s the maintenance  the differential before the cooling or heating gets started
               crew’s carelessness, is just cheap construction. I’ve seen  again. It’s not the best (remember I mentioned I wanted
               them ready to fall through the roof and so corroded that  ground source?) but my electric bills dropped to 38% of
               I wonder what’s preventing them collapsing. They sel-  what they were.
               dom use more efficient chilled water sources. Normal-     Instead of controlling the unit with a thermostat in
               ly they contain a complete refrigeration system with  the space or sensing temperature in the return air duct
               air cooled condensers and a DX coil. DX standing for  the outlet temperature of air conditioning apparatus can
               direct expansion which is an acronym that separates  be controlled by an independent system controller ac-
               them from separated systems that supply chilled water  cording to the lowest air temperature required at any
               and means the air is cooled directly by the refrigerant.  outlet in the air distribution system. All other outlets in
               Their operating cost is easily twice that of a unit using  the system control the temperature of supply air to the
               chilled water. They frequently are direct fired for heat-  space by a thermostat in that space through use of a re-
               ing which would be more efficient than steam or hot  heat coil or a variable air volume box.
               water from a boiler if the burners and controls weren’t     New regulations and design standards for build-
               so cheap that they are less efficient than a steam or hot  ing  ventilation  that  are  primarily  concerned  with the
               water operation.                                     distribution of the ventilation air have led to the intro-
                    I have spent an evening at a meeting in a local  duction of independent outside air supplies so don’t
               school during the winter listening to the RTU and con-  be surprised if some of your equipment doesn’t have a
               necting ductwork creak, snap, and  emit  other sounds  mixing box with connected outside air ductwork. Sep-
               that challenge a box of Rice Krispies (but  at several  arate air handling units, frequently called ventilation
               times the volume) while wondering if that night would  air units, provide outside air distributed to the building
               be when the ductwork or the RTU comes crashing down  through its own independent system of ducts and reg-
               because it has worked loose. Called for problems with a  isters. Those units can be operated to deliver air at the
               potential leak from an RTU I found it shifted on its curb  room design conditions so the ventilation air does not
               (a curb, by the way, is a raised portion of the roof that  have any effect on the operation of the heating and cool-
               supports one) until one corner of the RTU had slid over  ing equipment.
               enough to expose the indoors to the outdoors. They’re     One of the major considerations for load of an air
               where I find most of the access panels lacking half their  conditioning system is sun light. A well-designed sys-
               screws so unfiltered outside air leaks into them as well.  tem will account for variations in solar heat gain at dif-
                    If you’re stuck with operating and maintaining  ferent exposures (North, South, East, and West) through
               RTUs, may God bless you. All I can say about them is  the use of separate  AHUs, face and bypass dampers,
               do your best and pay attention to those creaks, moans  and/or reheat coils for each exposure. Of course the
               and snaps. If you can isolate them you may be able to  bigwigs  in  any  office  building  insist  on  having  corner
               eliminate them.                                      offices with double exposures and unless their space has
                                                                    independent temperature controls there will be periods
               Air Conditioning Systems Control                     when other occupants of the zone are uncomfortable.
                    The normal air conditioning apparatus control con-
               sists of a thermostat that starts and stops the fan, com-  The TAB Report
               pressor and associated electrical equipment. That would     In  any  large installation the  construction project
               be typical of our good old window units and the system  usually calls for air balancing. Technicians will take
               in your home. While it’s inexpensive at first cost the op-  readings and adjust air flows and temperatures, record
               erating costs are considerably higher than equipment  them, and show the actual measured air flow at each ap-
               that can operate continuously and modulate to control  paratus, main distribution duct, VAV boxes, and regis-
               space temperatures. When I had my heat pump replaced  ters. That document should also be kept handy so you
               I had the new one fitted with a two speed scroll com-  can compare the setup conditions with actual.
               pressor. It means the fan runs more but the compressor
               shifts back and forth between half and full speed (hi and  Convectors
               lo on the thermostat) to keep it running longer, some-     Convectors are usually floor mounted and usually
               times constantly at high heating and cooling loads. Ev-  below windows. They contain their own fan or fans to
               ery time a compressor shuts down the refrigerant pres-  circulate room air over refrigerant or water coils cooling
               sures balance out and the compressor has to reinstate  and/or heating the room air to adjust the room air for