Page 211 - Boiler_Operators_Handbook,_Second_Edition
P. 211

196                                                                               Boiler Operator’s Handbook

               problems with occupant comfort and resolve them or  warranty so the problem belongs to someone other than
               provide the owner with your analysis and suggestions  the owner, you should try to identify changes in load to
               for what a contractor would be needed to do.         see if they can be rectified. Look for any changes that
                                                                    increased the load and inform the owner of them.
               Data Collection and Analysis                             To check a problem with an AHU or RTU collect
                    Using a psychrometer depends on what type you  and record the actual temperature and air flow data for
               have. Call me old-fashioned but I prefer to use a good  that unit and mark a copy of the pyschrometric chart
               old sling psychrometer, the one shown in Figure 5-50.  you prepared with that unit’s design data to see what
               All I have to do is check that the wet bulb portion has  might be off.
               water in the reservoir. You can use an electronic gadget     Since the air carries the heat away, or delivers it to,
               but I suggest you make sure it’s calibrated every time  the occupied spaces a lack of adequate air flow should
               before you use it for serious work, especially if you’ve  be addressed first. Problems with unit air flow are com-
               dropped it. Yes, I’ve dropped the sling, and I’ve tapped  monly dirty filters followed by loose fan belts. For rooms
               some furniture while using it several times, but I haven’t  and zones VAV box filters should be checked followed
               broken it yet. And, since the gradations are on the ther-  by isolating a loose splitter damper, control damper,
               mometers it’s always right if it isn’t broke.        dirty reheat coil, and failed or damaged ductwork. Note
                    Progressively isolate the problem, determine if it’s  changes in the space that might have produced the prob-
               just one room, one zone, or affecting everything served  lem; I recall one where a contractor replaced all the ceil-
               by one piece of air conditioning equipment. Then check  ing tile in an office area, including replacing the return
               the obvious things: Is the equipment running? Does  it  air grills that allowed room air to return to the AHU.
               have electric and control power? Has someone tampered  The project manager told me the contractor complained
               with the thermostat or done something to block air flow?  that he had to clip down all the new ceiling tiles because
                    In checking a problem with a room or zone col-  they kept popping up. Other unique problems included
               lect and record room and supply air temperatures then  one where a contractor adding sprinkler piping had re-
               use the flow hood (Figure 5-47) to measure the air flow  moved the flex connections between the ductwork and
               through the registers. If the difference between room air  registers to get the pipes into the ceiling space. That was
               and supply air temperature is equal to or exceeds de-  revealed by return air temperatures considerably differ-
               sign, air flow through the registers is equal to or exceeds  ent than room air temperature; the air was flowing, not
               design and supply air wet bulb temperature is equal to  into the room but bypassing it.
               design or when cooling less, when heating more, then     I could fill this book with many more stories, each
               the system is working properly. That normally means  a lesson in what can go wrong, but you’ll have to apply
               the load in the room or zone is more than design and the  what you understand the systems are supposed to do to
               equipment simply can’t handle it.                    isolate problems with them. I can’t possibly tell you ev-
                    Unless it’s a new facility, which should be under  ery possible scenario within the page limit of the book.



















                         Figure 5-50. Sling Psychrometer                     Figure 5-51. Infrared Thermometer
   206   207   208   209   210   211   212   213   214   215   216