Page 209 - Boiler_Operators_Handbook,_Second_Edition
P. 209

194                                                                               Boiler Operator’s Handbook

               comfort. Many use the thermostat control to start and
               stop the fans while others will regulate the flow of the
               fluids through the coils. Ventilation is normally achieved
               by a small damper connecting to the outside so the fans
               will draw air in when they are operating. Refrigerant or
               chilled water coils will remove moisture from the room
               air by condensing it and the drain is typically run out
               the building wall but can be piped indoors. Convectors
               can be supplied with or without filters so filter replace-
               ment or regular cleaning of the unit is required. Convec-
               tors can  also  be two-pipe or  four-pipe. Two pipe  con-
               vectors use the same coil for heating and cooling, using
               heated or chilled water supplied by the central system.
               These require the operator monitor the weather, decide
               whether the building is to be heated or cooled and set up
               the system to deliver water at the required temperature.      Figure 5-49. Pitot tube application
               Modern convectors sense the temperature of the water
               supplied and automatically switch the thermostat re-  mined by a formula equal to 1.3 multiplied by the width
               sponse to control the flow of the water or the operation  times depth of the square duct multiplied and raised to
               of the fans. Four-pipe convectors have separate cooling  the 0.425 power divided by the sum of width and depth
               and heating coils and can heat or cool independent of  raised to the 0.25 power. Width and depth are simply
               the weather.                                         the two horizontal dimensions for vertical ducts.  You
                                                                    should also be able to find a table for equivalent round
               Achieving Comfort for Occupants                      duct sizes in one of the books available from the manu-
                    If someone is not comfortable you can count on re-  facturers of your air conditioning equipment. Test ports
               peated complaints and, in some cases, direct orders to  should be on two quarter points of round ducts and at
               do something about it. Unlike when they’re home, the  least four on one side of a square duct. The more read-
               occupants are seldom able to walkover and adjust the  ings you take, the more accurate your calculated result.
               thermostat because it’s seldom that the entire occupancy  You connect the manometer to both ports on the pitot
               is satisfied so the thermostat is locked up or concealed  tube so you’re getting velocity pressure, the difference
               because some people produce excessive adjustments  between total pressure and static pressure. Velocity (in
               that result in additional heating or cooling expense. The  feet per minute) at each measurement is determined by
               first step is determining what the space conditions are  multiplying the square root of the velocity pressure (in
               and that involves using a sling psychrometer (Figure  inches of water column) by 4006. (I use 4006 because
               5-50), a flow hood (Figure 5-47), a manometer set at a  there are competing groups that call it 4005 and 4007)
               ten to one slope (Figure 2-3), pitot tube (Figure 5-49) an  With  round  ducts  calculate  the  area  of  quarter  points
               infrared thermometer (Figure 5-51) and a scientific cal-  sampled in square feet and multiply by the velocity for
               culator. I mention these early on because you might just  the flow in that quarter for small ducts. For larger round
               be assigned to operate systems in a new installation and  ducts determine the area in segments and multiply by
               discover some of this equipment left behind by the in-  the calculated velocity in that segment. For square ducts
               staller or TAB (temperature and air balance) personnel.  it’s much easier to simply select equal rectangles (that
               If so, you’ll recognize it and put it away for your own  sometimes come out to be squares) centered on each
               future use. Much of the equipment and tools that still  measured point, and multiply that area by the measured
               clutter the trunk of my car came from that source.   velocity.
                    A combination of the manometer and pitot tube       Even when the air in a space is within the comfort
               is used to determine air flow in a run of ductwork. It’s  zone there may be other factors that affect the comfort
               great for checking for leakage in a long duct run. For  of the occupants. These can be attributed to solar insola-
               best results the rest ports should be located twenty di-  tion, warm ceilings, cold floors, warm or cold walls and
               ameters downstream and four diameters upstream of  drafts; any one of which can result in more than 50%
               any change in the duct (elbows, transitions, etc.). Oh, for  of the occupants being uncomfortable. Now you know
               square ducts use an equivalent round diameter deter-  why you need those instruments, you need to identify
   204   205   206   207   208   209   210   211   212   213   214