Page 206 - Boiler_Operators_Handbook,_Second_Edition
P. 206

Refrigeration & AC                                                                                  191

               stands for variable air volume. The space control ther-  produce  a  differential  measurement  that  indicates  air-
               mostats are used to regulate the flow of conditioned air  flow. This permits a quick comparison of actual airflow
               into the spaces to maintain the space dry bulb tempera-  to  the  design  airflow  shown  on  the  drawings.  Before
               ture.  Varying  the  airflow,  however,  can  create  difficul-  long I imagine the low-cost differential pressure sensors
               ties with space ventilation. Passing of small clouds that  will  permit  you  to  check  the  airflow  in  any  zone  at  a
               block sunlight to one or two rooms of a zone served by  remote terminal. You’ll need to use some judgment in
               the same VAV box can produce detectable temperature  monitoring the airflow because the loads served by the
               swings in those rooms just like systems on reheat coils.  VAV box are seldom at design conditions. Most of the
               A VAV box maintains temperature control in the room  time however, you’ll be looking at a problem during
               or zone by varying the quantity of conditioned air sup-  periods of maximum load where the readings will be
               plied to the room or zone. All the VAV boxes served by  meaningful.
               one piece of apparatus are supplied conditioned air to     A VAV box can be a simple device consisting of
               serve the largest load of the group so, theoretically, only  nothing more than an enclosure with a damper con-
               one or two VAV box dampers will be wide open at any  trolled by a modulating motor to open or close the damp-
               time. As long as the loads served by that air handling  er depending on the temperature in the space served by
               unit change uniformly no room supplied by a VAV box  the air passing through the VAV box. One VAV box can
               will have its damper throttled so much that the air regis-  serve several offices along one exposure of one floor of
               ters cannot mix the conditioned and room air enough to  an office building. Because of multiple exposures (sun-
               prevent poor ventilation and drafts. Despite that many  light being the major load in most air conditioning sys-
               systems are now installed with separate ventilation air  tems)  corner  offices  typically  require  an  independent
               supplies.                                            VAV box. That’s not always the case when the box serves
                    Some VAV boxes are fan powered to provide the  all offices along one building wall and, since the higher
               differential pressure required for proper distribution of  up gets the corner office, the thermostat is in the corner
               conditioned air into the space. Electrical savings are re-  office. When space utilization or heating or cooling load
               alized when those fans are shut down during periods of  varies such as interior versus exterior exposures, office
               no occupancy. The fans in the VAV boxes do not vary air-  space versus conference room, operating room in a hos-
               flow because the airflow has to be maintained to provide  pital compared to a patient’s room, separate VAV boxes
               proper mixing of supply and room air at the registers.  are normally provided. Changes in use of a space, in-
               So, the fan takes a suction on the inlet of the supply air  stallation of partitions and the like can make space tem-
               after the VAV box damper and a return air connection  perature control impossible. So, despite the advantages
               from the conditioned space.                          of VAV boxes satisfying everyone isn’t always possible.
                    VAV boxes serving rooms or zones at the sides of     The variable speed drive of the fan is controlled to
               the buildings, or under the roof, are typically fan pow-  maintain a constant pressure at one or more points in
               ered and include a heating coil to absorb the load of heat  the distribution system. Cooling and fan motor horse-
               losses to cold outside air. These are normally fitted with a  power are saved by these systems while simultaneously
               filter in their return air connection to prevent accumula-  providing more precise cooling and heating in the con-
               tion of dust and airborne debris in the fins of the heating  ditioned spaces.
               coil and on the fan (the conditioned air should be clean).
               Most of these maintain temperature control during the  Air Registers and Diffusers
               winter  and  on  cold  days  by  throttling  the  flow  of  the     Registers, typically in walls and floors, and diffus-
               heating medium, usually hot water, through the heating  ers, usually devices installed in the ceilings of the rooms,
               coil. Since those filters are always in service monitoring  are designed to mix conditioned supply air with room
               of their condition until an optimal replacement period is  air to  absorb  most of  the rising  heat  load  when  cool-
               established is an added predictive maintenance require-  ing. The intent of the design is to mix the air to within
               ment for a new system. Other than situations where  a couple of degrees of the room air temperature before
               the air in the zone can be contaminated inconsistently  it strikes a wall or occupants to produce sensations of
               during regular activity a filter replacement program can  draft. There is little need for concern with the delivery of
               be established with longer periods between replace-  heated air because very few occupants object to warmer
               ments than those recommended by the manufacturers.   temperatures of delivered air in the heating season.
                    Almost all VAV boxes are fitted with airflow sen-     Temperature controlled registers that vary the de-
               sors that normally permit connection of a manometer to  livery of supply air by throttling the flow of air through
   201   202   203   204   205   206   207   208   209   210   211